1 GENERAL NOTES P-89747 <br /> N EQUIPMENT LIKELY TO BE WORKED UPON WHILE <br /> 1 ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT <br /> , - 1 SATISFY MINIMUM WORKING CLEARANCES PER NEC <br /> ,f SECTION 110.26. <br /> CONTRACTOR SHALL USE ONLY COMPONENTS LISTED <br /> BY A NATIONALLY RECOGNIZED TESTING LABORATORY <br /> FOR THE INTENDED USE. <br /> CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL <br /> (' °'z'•• EQUIPMENT,CABLES,ADDITIONAL CONDUITS, <br /> RACEWAYS,AND OTHER ACCESSORIES NECESSARY IJ 1 <br /> .e._-,.+w>!x� i.f..`.,�. v,- FOR A COMPLETE AND OPERATIONAL PVSYSTEM. <br /> -M - C/) <br /> WHERE DC PV SOURCE OR DC PV OUTPUT CIRCUITS <br /> ARE RUN INSIDE THE BUILDING,THEY SHALL BE <br /> CONTAINED IN METAL RACEWAYS,TYPE MC METAL- N Lo <br /> CLAD CABLE,OR METAL ENCLOSURES FROM THE POINT ly- w M <br /> OF INTO THE BUILDING TO THE4 READIL ACCCEISSIB E DISCONNECTING MEANS,IRST PER L.LI Q J <br /> - m- NEC SECTION 690.31(G). LL- <br /> ALL EMT CONDUIT FITTINGS SHALL BE LISTED AS 0 = <br /> ' - WEATHERPROOF FITTINGS AND INSTALLED TO ENSURE J <br /> A RAINTIGHT FIT,PER NEC SECTION 358.42. <br /> v.> _M 2 <br /> IN PROPOSED ROOF-MOUNTED PHOTOVOLTAIC 0 <br /> ARRAY.8:12(34°)SLOPED ROOF,23 PV MODULES C) <br /> > II (SILVER FRAME),179°AZIMUTH M <br /> • O2 (N)DISCONNECT(SWI),OUTDOOR LL uj <br /> N <br /> O3 (N)INVERTER(11),OUTDOOR Q <br /> (N)TRANSITION BOX(J131),OUTDOOR,OUTPUT <br /> 1 SITE PLAN AERIAL VIEW O CIRCUIT CONDUCTORS SHALL 8E RUN IN EMT <br /> 4 CONDUIT OVER ROOF NO CLOSER THAN 0.5'ABOVE 0 <br /> PV-2 SCALE:1°=20' ROOF SURFACE <br /> SITE PLAN <br /> DOC ID:89747-111511-1 <br /> DATE:6/1/18 <br /> CREATOR:S.S. <br /> REVIEWER: <br /> REVISIONS <br /> PV-2 <br />