Laserfiche WebLink
Single Family Dwelling <br /> Pl <br /> an-Review Comments <br /> l: F.F.E. shall be,a minimum of 87 above.the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to.comply with R401.3 of the-F.B:C: <br /> 3. :Compactioh esi required.if 24" or more of-fill dirt is-brought in:, any one place: <br /> 4: Tie in surveyreuired before pouring concrete. <br /> .5. Dnveways:require a R:O:W. use permit. A114:sides of driveway thru the sidewalk shall Have <br /> expansion material: <br /> 6. All setbacks shall be met.- . <br /> 7. All property markers shall be uncovered and marked at time off rst.inspection: <br /> 8: :All A.D.A. requirements shall be meta <br /> 9. No electric;plumbing, mechanical,,or training shall be covered without an inspection and <br /> approval first. . <br /> 10. All Garages shall comply.with section R302:6.of.the F.B.C::(Fire S.eparation). <br /> I I. Appliances shall not be installed_ in-a location where subject to,mechanical damage:unless. <br /> protected by approved barriers. M303.4 of the F.B:C <br /> 12. Water heaters'shall comply with secti6nP607.3 of the F.B.C. <br /> 13. Foundation supports`for.A/C.units shall be raised at least.3 above finished grade.. M1308.1 <br /> 14.Return air in all;bedrooms. F.B.C. .M1620:4.. <br /> 15. Smoke detectors are to be installed:in accordance:with R313.1 of the F.B.C. <br /> 16: All glazing requirements are to be in accordance with R308.4 of the F.B.C. <br /> 17. All means of egress are to be in accordance with R31 L:of the F:B.C. <br /> 18. `.`Green gypsum board shall not be used:as a backer.in showers or tubs.R702.4.2.F.B.C. <br /> 19. Combination-type AFCI breakers,are required at all,locations requiring an AFCI,type breaker: <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil-buining heating <br /> or appliances or an attached garage: They shall be,mstalled'in accordance with.the F,B.C.- <br /> . <br /> 21. All plumbing, mechanical,.and electrical shall be separate from unit to,unit: This includes all <br /> underground plumbing and electric: <br /> . ..22. All 2616-ME:C:. Codes:will-be enforced.. <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11 of the-2016 N.E:C . <br /> 24. In accordance.with the Land Development.Code, lots shall be sodded before final at least 10.. <br /> feet around the structure. <br /> 25. Blower door test and blown in insulation card shall be provided before C.O.. <br /> 26 A_copy of the energy eaclsshall be with permit at all tinier <br /> 27-. Copy of final insulation report shall be:provided*with:permit before.finab. <br /> F.F.E.-Finished Floor Elevation <br /> F:B.C- Florida Building Code 6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2011) <br />