FIRE SAFETY REQUIREMENTS P-99764 <br /> H 'EXTERIOR-MOUNTED OC CONDUITS,WIRING SYSTEMS, <br /> AND RACEWAYS FOR PHOTOVOLTAIC CIRCUITS SHALL <br /> BE LOCATED AS CLOSE AS POSSIBLE TO THE RIDGE, <br /> x. 1 HIP,OR VALLEY,AND FROM THE HIP OR VALLEY AS <br /> 5 DIRECTLY AS POSSIBLE TO AN OUTSIDE WALL TO <br /> REDUCE TRIP HAZARDS AND MAXIMIZE VENTILATION <br /> rN OPPORTUNITIES(NFPA 1 11.12.2.2.4.1) <br /> w ;S <br /> p �a ROOF ACCESS POINTS SHALL BE DEFINED AS AREAS <br /> WHERE FIRE DEPARTMENT LADDERS ARE NOT PLACED <br /> j, OVER OPENINGS(WINDOWS OR DOORS).ARE LOCATED <br /> 2 AT STRONG POINTS OF BUILDING CONSTRUCTION,AND w <br /> ARE IN LOCATIONS WHERE THEY WILL NOT CONFLICT F- <br /> 1 WITH OVERHEAD OBSTRUCTIONS(TREE LIMBS,WIRES, CA CV <br /> OR SIGNS).(NFPA 111.12.2.2.1.3) Cn U ' <br /> PHOTOVOLTAIC MODULES SHALL BE LOCATED IN A <br /> �\y '; ���• MANNER THAT PROVIDES TWO 3 FTWIDE ACCESS ofz M <br /> PATHWAYS FROM THE EAVE TO THE RIDGE ON EACH UJ Lu c7 <br /> ROOF SLOPE WHERE THE MODULES ARE LOCATED. —1 <br /> (NFPA 111.10.2.2.2.1.2) � O O LL <br /> 4 PHOTOVOLTAIC MODULES SHALL BE LOCATED NO LESS W Cn <br /> THAN 3 FT BELOW THE RIDGE.(NFPA 111.10.2.2.2.2) X J <br /> ✓,y"°- Q o <br /> of LL <br /> ' s O 3.0 FT.WIDE SMOKE-VENTILATION SETBACK,PER NFPA J W <br /> 1' 111.10.2.2.2.2 O f- Ln >- <br /> OIll') a <br /> 1i.10.2.2.2.1.2 W N <br /> Oj ROOF ACCESS POINT,PER NFPA 111.12.2.2.1.3 )-- <br /> i <br /> 3'. CABLES,WHEN RUN BETWEEN ARRAYS,SHALL BE <br /> 4 ENCLOSED IN CONDUIT. <br /> 1 FIRE SAFETY PLAt401 <br /> PV-7 SCALE:1.'=20' <br /> FIRE SAFETY <br /> PLAN <br /> OC 53 0- <br /> DATE:10115118 <br /> CREATOR:S.S. <br /> REVIEWER: <br /> REVISIONS <br /> PV-7 <br />