At normal temperatures, the glass bulb contains the fluid Model F1 FR Series sprinklers must be installed with the <br /> in.both the liquid and vapor phases. The vapor phase can Reliable sprinkler installation wrench identified in the Design <br /> be seen as a small bubble. As heat is applied, the liquid and Installation Information table in this Bulletin. Any other <br /> expands,forcing the bubble smaller and smaller as the liq- wrench may damage the sprinkler. A leak tight sprinklerjoint <br /> uid pressure increases. Continued heating forces the liquid can be obtained with a torque of 8 to 18 lb-ft(11 to 24 N-m). <br /> to push out against the bulb, causing the glass to shatter, Do not tighten sprinklers over the maximum recommended <br /> opening the waterway and allowing the deflector to distrib- installation torque. Exceeding the maximum recommended <br /> ute the discharging water. installation torque may cause leakage or impairment of the <br /> Model F1 FR Series sprinklers provide a wide range of op- sprinkler. <br /> tions where quick-response,glass bulb sprinklers are used: Recessed Sprinklers <br /> • Pendent, recessed pendent, upright, horizontal Model F1 FR Series Recessed sprinklers are to be installed <br /> sidewall, and vertical sidewall deflectors as shown in Fig. 1,Fig.2,or Fig.3,as applicable to the spe- <br /> • K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60 cific model being installed.The Recessed Escutcheon Data <br /> metric), and 5.6 (80 metric) table in the Bulletin identifies the only recessed escutcheons <br /> • Flush, recessed, and concealed installations that are permitted to be used with each Model F1 FR Series <br /> See the Design and Installation Information table in this Recessed sprinkler.The use of any other recessed escutch- <br /> Bulletin for information on the approvals and availability of eon will void all approvals and negate all warranties. <br /> specific Model F1 FR series sprinkler configurations. Concealed Sprinklers <br /> Model F1 FR Recessed Pendent and Recessed Horizon- Model F1 FR Series Concealed Pendent sprinklers are to <br /> tal Sidewall sprinklers are required to be used with Reliable be installed as shown in Fig.4 or Fig.5,as applicable to the <br /> Model F1, F2, or FP recessed escutcheons. See the Re- selected cover plate. Model F1 FR56 Concealed Pendent <br /> cessed Escutcheon Data table in this Bulletin for listing and and Model F1 FR56LL Concealed Pendent sprinklers have <br /> approval information with each specific Model F1 FR series a factory-installed Model CCP cup. A protective cap is in- <br /> sprinkler.Model F1 and F2 recessed escutcheons,shown in stalled at the factory that should remain on the sprinkler until <br /> Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch the sprinkler is installed and should then be reinstalled on <br /> (19mm) and 1/2-inch (12.7mm) of adjustment, respectively. the_sprinkler until the cover plate is installed.The concealed <br /> Model FP recessed escutcheons,shown in Fig.2, provide a sprinkler assemblies are completed by the installation of a <br /> 1/2-inch(12.7mm)threaded adjustment. Model CCP push-on/thread-off cover plate assembly. The <br /> Model F1 FR56 Concealed Pendent and Model F1 FR56LL cover plate and sprinkler cup assemblies are joined using <br /> Concealed Pendent sprinklers are required to be used with a cover plate skirt with flexible tabs for threaded engage- <br /> Model CCP cover plates.A standard profile Model CCP cov- ment..A choice of two Model CCP cover plate assemblies <br /> er plate is available that provides up to 1/2-inch(12.7mrn)of provides either 1/2-inch (13mm) or 5/8-inch (8mm)of cover <br /> cover plate adjustment..ln addition,a low profile Model CCP adjustment. Do not install Model F1 FR Series Concealed <br /> cover plate is also available that provides up to 5/16-inch Pendent sprinklers in ceilings which have positive pressure <br /> (8.Omm) of cover plate adjustment. See the Design and In- in the space above. <br /> stallation Information and Listed and Approved Temperature Model F1FR Series Concealed Pendent sprinklers require a <br /> Ratings tables in this Bulletin for further information on ap- 2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The <br /> proved cover plate options. Model RC1 wrench is used to engage the sprinkler wrenching <br /> Application surfaces and to install the sprinkler in the fitting. Remove the <br /> Model F1 FR Series sprinklers are intended for use in protective cap to install the sprinkler,then reinstall the protective <br /> accordance with NFPA 13, FM Property Loss Prevention cap until the cover plate is installed. When inserting or remov- <br /> Data Sheets, and the requirements of the Authority Hav- ing the wrench from the sprinkler/cup assembly,care should be <br /> ing Jurisdiction. Care must be exercised that the k-factor, taken to prevent damage to the sprinkler. Do not wrench any <br /> temperature rating,deflector style, and sprinkler type are other part of the sprinkler/cup assembly. Installation is com- <br /> in accordance with the requirements of the applicable pleted by removing the protective cap from the sprinkler and <br /> design and installation standards. In addition, Model pushing the cover plate onto the Cup.Final adjustment is made <br /> F1 FR Series sprinklers must be used in accordance with by hand turning the cover plate until the skirt flange makes full <br /> their listings and approvals, as well as the information contact with the ceiling.Cover plate removal requires turning the <br /> provided in this Bulletin. cover plate in the counter clockwise direction.After installation, <br /> Installation inspect all sprinklers to ensure that there is a gap between the <br /> Glass bulb sprinklers have orange bulb protectors or pro- cover plate and ceiling and that the four cup slots are open and <br /> tective caps to minimize bulb damage during shipping,han- free from any air flow impediment to the space above. <br /> dling and installation. Reliable sprinkler installation wrench- Concealed cover plate/cup assemblies are listed only for <br /> es are designed to install sprinklers with bulb protectors in use with specific sprinklers.The use of any concealed cover <br /> place.Remove the bulb protector at the time when the sprin- plate/cup assembly other than the Reliable Model CCP with <br /> kler system is placed in service for fire protection. Removal Model F1 FR56 Concealed Pendent and Model F1 FR56LL <br /> of the bulb protector before this time may leave the bulb vul- Concealed Pendent sprinklers or the use of the Model CCP <br /> nerable to damage.Remove bulb protectors by undoing the Concealed cover plate assembly on any sprinkler with <br /> clasp by hand. Do not use tools to remove bulb protectors. which it is not specifically listed my prevent good fire pro- <br /> tection and will void all guarantees, warranties; listings and <br /> approvals. <br /> 2. <br />