Laserfiche WebLink
Buildin Anal SIS Job: 1551B1 sf ADS Carrier <br /> g Y Date: 511/2018 <br /> Entire House By: Dave <br /> BAYONET PLUMBING COOLING HEATING <br /> Project Information, <br /> For: Lennar Homes <br /> Design Conditions <br /> Location: Indoor: Heating Cooling <br /> Tampa International AP, FL, US Indoor temperature(°F) 70 75 <br /> Elevation: 10 ft Design TD (°F) 39 16 <br /> Latitude: 28°N Relative humidity (%) 50 50 <br /> Outdoor: Heating Cooling Moisture difference(gr/lb) 34.7 54.7 <br /> Dry bulb(°F) 31 91 Infiltration: <br /> Daily range(°F) - 14 ( L ) Method Simplified <br /> Wet bulb(°F) - 77 Construction quality Semi-tight <br /> Wind speed(mph) 15.0 7.5 Fireplaces 0 <br /> Component Btuh/ftZ Btuh % of load <br /> Walls 5.6 6121 28.1 Ducts <br /> Glazing 30.2 3154 14.5 wall nfiltration <br /> Doors 23.5 480 2.2 <br /> Ceilings 1.3 1950 8.9 <br /> Floors 3.7 5815 26.7 <br /> Infiltration 1.9 2372 10.9 <br /> Ducts 1901 8.7 <br /> Floors <br /> Humidification 0 0 Glazing <br /> Ventilation 0 0 iDoors Ceilings <br /> Adjustments 0 <br /> Total 21794 100.0 <br /> Component Btuh/ftZ Btuh % of load <br /> Walls 2.8 3045 16.2 Walls <br /> Glazing 59.1 6179 32.8 Internal Gains <br /> Doors 18.4 376 2.0 <br /> Ceilings 1.7 2697 14.3 <br /> Floors 0 0 0 <br /> Infiltration 0.4 531 2.8 <br /> Ducts 2200 11.7 Ducts <br /> Ventilation 0 0 <br /> Internal gains 3808 20.2 Glazing Infiltration <br /> Blower 0 0 <br /> Adjustments 0 Ceilings <br /> Total 18835 100.0 Other <br /> Latent Cooling Load=2542 Btuh <br /> Overall U-value= 0.103 Btuh/ftZ-°F <br /> Data entries checked. <br /> - -Ofi- =ightsoft- 2018-May-01 08:15:01 <br /> ^�^ -„..... Right-Suite®Universal 2018 18.0.16 RSU05714 Page 1 <br /> ..equipment\1551 sf ADS template 2ton Carrierrup Calc=MJ8 Front Door faces: W <br />