Laserfiche WebLink
GENERAC <br /> CORNERSTONE AIR <br /> 4946 LAND O LAKES BOULEVARD <br /> LAND O LAKES,FL 34639-4418 <br /> (813)949-4445 <br /> Sizing Report <br /> Rated Nominal Voltage 240 <br /> Generator Fuel Choice Propane <br /> Sizing Method(NEC 220) Part IV <br /> (Part III required for selected circuit implementation,Both valid for whole house) <br /> General Lighting&Receptacles Load(kW) <br /> Square Footage Being Covered(ftA2) 1844 5.532 <br /> Small Appliance Circuits(20 amps) <br /> Kitchen Circuits 2 3 <br /> Laundry Circuits 1 1.5 <br /> Managed Estimated Nameplate <br /> Fixed-In-Place Appliances&Motors Loads (kW) (amps) 240 V Load(kW) <br /> Dryer X 5.5 X 0.0 <br /> Microwave 1.3 1.3 <br /> Range-Oven w/Top 8.5 X 8.5 <br /> Furnace(Forced Air) 0.7 0.7 <br /> Water Heater 5.0 X 5.0 <br /> Dishwasher 1.5 1.5 <br /> Refrigerator 0.8 0.8 <br /> washer 0.0 2 0.2 <br /> disposal 0.0 2 0.2 <br /> Managed Estimated Nameplate <br /> Air Conditioning&Cooling Loads (kW) (amps) 240 V Load(kW) <br /> Managed Estimated Nameplate <br /> Heating&Heat Pumps Loads (kW) (amps) 240 V Load(kW) <br /> Heat Pump(3.5 Ton) 3.5 X 3.5 <br /> Estimated Actual Utilized <br /> Transient Requirement (LRA) (LRA) (LRA) <br /> Largest Motor's Starting Amps(LRA) 101 112 112 <br /> Load NEC <br /> Summary NEC Load (kW) Required <br /> General Lighting&Receptacles 10 <br /> Fixed-in-Place Appliances&Motors 18.2 <br /> Sum of all General Loads 28.3 17.3 <br /> Cooling 0 0 <br /> Heating(w/demand factors) 3.5 3.5 <br /> Larger of Heating&Cooling 3.5 3.5 <br /> Sizing based on requirements of NEC Article 220,Part IV 20.8 <br /> Elevation 0 ft <br /> Minimum size generator for motor starting requirements 16 <br /> BTU load required 350000 <br /> 22 kW Generac Model Generator Recommended <br />