Laserfiche WebLink
Sing: e Famil Dwell" <br /> Y. . g <br /> Pl <br /> an Review.Comments <br /> 1. F.F.E. shall be a minimum of 8" above-the_road elevation and an engineered.site plan. <br /> 2.. Lots-shall be graded to.comply with R401.3 of the F.B.C. <br /> 3. Compaction:test required if 24" or more of fill dirt is brought in at any one place: <br /> 4: 'Tie in survey required before pouring concrete. <br /> 5.: Driveways.require a R.-O.W. use permit: All 4:sides of driveway thru the sidewalk shall have <br /> expansion material:. <br /> 6.. All setbacks shall be met. <br /> 7. ;All.property_markers shall be uncovered and marked at time of firstinspectiori: <br /> 8: .All A.D.A.-requirements shall be met.:'. <br /> 9. No:electric-plumbing, mechanical, or-framing shall be covered without an inspection and <br /> approval first. . . . .. . <br /> 10..All Garages shall:comply_with,section R302.6,of the.F.B:C- (Fire Separation).. <br /> 11.Appliances shall not installed in.a locationwhere subject to mechanical damage iiriless. <br /> :protected by approved barriers. M303..4 of.the F.B.0 <br /> 12. Water heaters shalt Y p <br /> com 1 .with sectionT607.3 of the F.R.C. <br /> 13.Foundation supports for.A/C.units shall be raised at least T.' above finished grade.. M 1308.1. <br /> 14. Return airin all bedrooms. F.B.C. .M.1620.4_ <br /> 15: Smoke detectors are.to beinstalled:iri accordance.witli:R313:.1 of the:F.B.C. <br /> .16. All glazing requirements are..to be'in accordance with R308.4.of the F.B.C. <br /> 17. A11 means of egress-are to:be in.accordance with R311::6f the F:B.C., <br /> 18. `Green gypsum board" shall riot be used as.a backer in:showers or tubs:R702.4:2.F.B.C. <br /> 19.-Combination-type'AFCI breakers are.required:at all locations requiring-an AFCI-type breaker: <br /> 20. Carbori monoxide alarms will be required in new:construction that-uses.fossil-burning heating <br /> or appliances or an attached garage: They shall be,installed in accordance with the F.B.C: <br /> 21. All plumbing,mechanical,:and electrical shall be separate from unit_to:unit: This includes all. <br /> underground plumbing and electric. <br /> 22.:All 2016:N.E.C. Codes Will be enforced.. <br /> 23.Tamper=Resistant Receptacles in accordance with 406:1 l of the 2016 N.E:C <br /> 24.1h accordance with the Land..Development:Code;lots shall be sodded before final of least 10 <br /> feet around;the structure. <br /> 25. Blower door test and blown in insulation-card shall be provided before C.O. <br /> 26..A copy of-the energy caels.shall be with permit-at all tinier <br /> .27.. Copy of final insulation report-shall be:provided)Wth:permit before:finab <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-Florida Building Code.6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A:-Americans with Disabilities Act N.E.C.-National Electric Code(2011) <br />