Single Family Dwelling <br /> Plan Review Comments <br /> 1: F.F.E. shall be;a mnirnum.of 8" above.the road elevation-and an engineered site plan. <br /> 2.- Lots shall be graded to-comply with R401.3 of the-F.B:C: <br /> 3.- Compaction-test required.if 24" or more of fill dirt is brought in at any one place'..'. <br /> 4. :Tie in surveyrequired before pouring concrete. <br /> 5. Driveways require a R:O:W. use permit.. All.4:sides 'of driveway thru the-sidewalk shall.have. <br /> expansion material:. <br /> 6. .All setbacks-shall be met. <br /> 7.- All pro pertv markers shall be.uncovered and marked at time of first 'inspection. <br /> 8. All A.D.A.-requirements.shall be met." <br /> 9.' No electric,plumbing,inechanical,.or framing shall be covered without an.inspection and <br /> approval first. . <br /> 10. All Garages shall:comply,with:section R302.6 of the.F;.B.C.:.(Fire Separation).. <br /> 11:Appliances shall iiot be installed in.a location where subject to niechanical damage unless <br /> protected by approved barriers. M303.4 of the F.B.0 <br /> 12. Water:heaters shall comply with section P607.3 of the F.B.C. <br /> 13. Found`atiori supports for.A/C units shall be raised at least 3 above finished-grade.. M1308.1. <br /> 14. Return air in all,bedrooms. F.B.C. M.1620:4 <br /> 15. Smoke detectors are-to b-e installed:in accordance=WiihR313:.1 of-the F.B.C. <br /> 16: All glazing requirements are.to be in accordance with R308.4.of the F.B.C. <br /> 17. All means.of egress are to,be in.accordance with R31 Yof the F.B.C... :: <br /> 18. "Green gypsum.board" shall riot be used as.a backer.in.showers or tubs. R702.4.2 F.B.C. <br /> 19.'Combination-type A. I breakers are,required at all locations requiringnAFCI,tpebreaker: <br /> 20. Carbon monoxide alarms:will be required in,new:construction that uses fossil-burning heating <br /> or appliances or an attached garage.:. They shall be,installed in accordancewith the F,B.C: <br /> 21. All plumbing,mechanical, and electrical shall be separate from unit to unit: This includes all <br /> Underground plumbing and electric: <br /> 22. All 2016 N.E.C;. Codes,will be enforced. <br /> 23.Tamper-Resistant Receptacles in accordance with 406:11 of the 2016 N.E:C <br /> 24 1h accordance:with the Land.Development:Code,lots,shall be.sodded'before final at least 10 <br /> feet around:the structure... <br /> 25.-Blower doof test and blown in insulation card shall be provided before CO.. <br /> 26.A copy�ofthe enemy cacls.shall be with perinit.at-all tines <br /> 27. Copy of final insulation report shall be:provided.with:permit before:fcncab . <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-;Florida Building Code 6th.Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2011) <br />