Laserfiche WebLink
Manual S Compliance Report Job: 1941B1 sf ADS Carrier <br /> Date: 8/13/2018 <br /> Entire House By: Dave <br /> Bayonet Plumbing Heating and Air <br /> Project Information <br /> For: Lennar Homes <br /> Cooling Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.3°F Sensible gain: 26154 Btuh Entering coil DB: 75.6°F <br /> Outdoor design WB: 77.3°F Latent gain: 4080 Btuh Entering coil WB: 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 30234 Btuh <br /> Indoor RH: 50% Estimated airflow: 1200 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP <br /> Manufacturer: Carrier Model: 25HBC536A00300+FX4DNF037L <br /> Actual airflow: 1200 cfm <br /> Sensible capacity: 29580 Btuh 113% of load <br /> Latent capacity: 5220 Btuh 128% of load <br /> Total capacity: 34800 Btuh 115% of load SHR: 85% <br /> Heating Equipment <br /> Design Conditions <br /> Outdoor design DB: 30.8°F Heat loss: 28843 Btuh Entering coil DB: 69.7°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SpIitASHP <br /> Manufacturer: Carrier Model: 25HBC536A00300+FX4DNF037L <br /> Actual airflow: 1200 cfm <br /> Output capacity: 26331 Btuh 91% of load Capacity balance: 28 °F <br /> Supplemental heat required: 2512 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip <br /> Manufacturer: n/a Model: n/a+n/a <br /> Actual airflow: 1200 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 °F <br /> Meets all requirements of ACCA Manual S. <br /> -�- wrightsoft® 2018-Aug-13 14:36:54 <br /> "� ..• «-»w. Right-Suite®Universal 2018 18.0.16 RSU05714 <br /> Page 1 <br /> ...equipment%1941 sf ADS template 3ton Carrier.rup Calc=MJB Front Door faces: W <br />