Single. Family Dwelling <br /> Plan Review Comments <br /> 1. F.F.E. shall be a minimum.of 8" above'the road elevation and an engineered.site plan. <br /> 2.. -Lots shall be graded.to comply with R401.3 of theF.R.C. <br /> 3. Compaction test required.if 24" or more of fill dirt is.brought in at any one place_ <br /> 4:. Tie in survey required before pouring concrete. <br /> Driveways require a R.O.W. use permit. All 4:sides of driveway thr i the sidewalk shall=have. <br /> expansion material: <br /> 6.. All setbacks.shall be met. . <br /> 7. :All.property:markers shall be.uncovered and marked.at time of first inspection: <br /> 8: All A.D.A.requirements shall be met. <br /> 9. No:electric,plumbing,mechanical;,or framing shall be covered without an.inspection and <br /> :approval first. <br /> 10.All Garages shall comply,.with;section R302.6 of the:F.B.C,:;(Fire Separation). <br /> 11:Appliances-shall not be installed in a location where subjectto.mechanical damage unless <br /> Y a <br /> p..rotected b roved barriers. M303.4 of the F.B:C <br /> . _ pp . . <br /> 12. Water,heaters shall comply.with sectionT607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units.shall be raised at least 3" above f Wished grade.. M1308.1. <br /> 14.Return air in all bedrooms.F:B.C. M1620.4 <br /> 15. Smoke detectors are to be installed in accordance with=R313:.1 of-the F.B.C. <br /> 16::All glazing requirements are.to be in accordance'with R308.4,of the F.B:C. <br /> 17. All means of egress are to be in:accordance-with R311 of the F.B.C. .. <br /> 18. `.`Green gypsum.board shall notbe used as, a.backer in' showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type.AFCI-breakers are.required at all locations requiring anAFCI,type breaker: <br /> 20. Carbon monoxide.alarms Will be required in.new construction that uses fossil-burning heating <br /> or appliances or an attached garage.. They shall be installed in accordance with.the F.B.C. <br /> 21. All plumbing, mechanical, and.electrical shall be separate from unit_to:unit: This includes a4 <br /> underground plumbing and electric. :. <br /> 22. All 2016.N.E.C. Codes will be enforced. <br /> 23. Tamper=Resistant Receptacles in accordance with 406.11 of the 2016 N.E:C <br /> .24,Ah accordance.With the Land Development.Code,dots shall be soddedbefore'final of least 10. . <br /> feet around.the structure. <br /> 25. Blower door test and blown in insulation card shall be provided before C.O. <br /> 26.A copyoof the enerzy caels.shall be with permit-at all tinier <br /> 27. Copy of final insulation i-eport shall be:pi•ovided with:perhiit before.final <br /> 28: 1Vo fence,pool or screen enclosure is issued with this nernzit <br /> F.F.E.-Finished Floor Elevation <br /> F.B.0 Florida Building Code 6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with,DisabilitiesAct N.E.C.-National Electric Code (2016) <br />