Laserfiche WebLink
Single ami Y we ing: <br /> Plan Review Comments <br /> 1: F.F.E. shall be a minimum of 8" above.the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to comply with R401.3 of the F.B.C. <br /> 3. Compaction.test required.:if24"or more of fill dirt is brought in.at any one place: <br /> .4. Tie in.survey required before pouring concrete.. <br /> 5. Driveways.require a R:O:W. use permit: All,_4 sides of driveway thra the sidewalk shall have <br /> expansion material:. <br /> 6. All setbacks-shall be met.: <br /> 7. All property markers shall be uncovered and in. at time of first inspection: <br /> 8. All A.D.A:requirements shall be met.. . <br /> 9. No electric`plumbing,.mechanical�.or frainirig shall be.covered without an.inspection_and - <br /> . g� . . . . . <br /> - : . .. approval first.:.. <br /> 10.All Garages shall,comply,with:section R302:6 of the:F.B.C:_(Fire Separation).: <br /> I L.Appliances shall not:be installed in:a location where subjectto mechanical'damage unless <br /> protected'by approved,barriers. .M303.4 of the F.B.0 <br /> 12. Water heaters shall comply:with section P607.3 of the F.B.C: <br /> 13. Foundation supports for A/C units shall be raised at least 37 above finished grade, M1308,1 <br /> - 14. Return air in all.bedrooms..F.B.C. .M1620.4, <br /> - : 15. Smoke detectors are to be installed i ' accordance.witli R313:1 of the F.B.C. <br /> 16. All glazing requirements are.to be in accordance with R308.4 of the F.B.C. <br /> 17. All means.of egress are to:be in accordance.with R31 l:of the F:B.C.- .: <br /> 18. "Green gypsum board shall not be-used-as a backer in:showers or tubs. R702.4.2.F.B.C. <br /> 19..Combination-type AFCI breakers.are required,at all.locations requiring an AFCI.type breaker: <br /> 20. Catbon monoxide alarms:will be required m-new:construction that uses-fossil-burning heating <br /> :or appliances or an attached garage.:. They shall be,installed'in accordance with.the F.B.C: <br /> 21. All plumbing, mechanical,:and.electrical shall be separate from unit to:unit: This includes all <br /> underground plumbing and electric. <br /> 22. A11201-6 N.E.C. Codes will be enforced. <br /> 23.Tamper-Resistant Receptacles in accordance with 406.11 of the 2016 N.E:C <br /> 24. In accordance:.with the Land Developmeiit:Code,lots shall be§odd-ed'before final at least 10_ <br /> feet around the structure. : . <br /> 25. Blower door test and blown in insulation card shall be provided before C.O. <br /> 26.A copy of the energy cdclsshall be with permit.at all times.. <br /> 27. Copy of final insulation report shall be.provided,with:perjnit before:rnal . <br /> 28:No fence;pool or screen enclosure is issued with this Permit- <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-Florida Building Code 6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />