- wrightsa ft" Manual S Compliance Report Jo
<br /> Entire Mouse By:
<br /> Progressive Air Systems, Inc Plan: Hayden 2605
<br /> 5907 Dasher Ct,Port Richey,FL 34668 Phone:727-847-3898 Fax:727-815-3399 License:CAC033669
<br /> ?;'?E° .• 'ir`sss. :^ y�;a+t+,v�.�,g e g•_,:a4; :'ir,",
<br /> i y?d-}e'< .�?£' .�wh04 ':-2d,: ,K:.,,s.
<br /> For: ,-, DR Horton
<br /> Lot 3 Blk 11 Silverado, Zephyrhills, FL
<br /> x,=: ,:�t"",.s� �'��,ta'z..�s�a.•:'�; .�, '.• c`�.,-.;„ ..ems �.p- ® ,©
<br /> ^
<br /> .„::~%<?': , >G ,,,, ,,..'k$-sr.,,C,rt's.5.,£, „-�?'....g�a, 'b;.t'' �,{s,'#;�'s .< kx.r,-•e���..-a yro; ,as-*.:'-F,.�u 7,�T:�'Y"'�''"��.s
<br /> Design Conditions
<br /> Outdoor design DB: 91.2°F Sensible gain: 30013 Btuh Entering coil DB: 76.4°F
<br /> Outdoor design WB: 77.1°F Latent gain: 4144 Btuh Entering coil WB: 63.2°F
<br /> Indoor design DB: 75.0°F Total gain: 34157 Btuh
<br /> Indoor RH: 50 Estimated airflow: 1367 .cfm
<br /> Manufacturer's Performance Data at Actual Design Conditions
<br /> Equipment type: Split ASHP
<br /> Manufacturer: Carrier, Model: CH14NB042****A+FB4CNP042
<br /> Actual airflow: 1367 cfm
<br /> Sensible capacity: 32445 Btuh 108%of load
<br /> Latent capacity: 6269 Btuh 151%of load
<br /> Total capacity: 38714 Btuh 113%of load SHR: 84%
<br /> 'g�;'sv. �� °a:,r;�•�-fa`�`'µ�`= ,: �x, �>'> � 0 F $ 9 ,�,'= t 9:. r�`sa :a...s,»as",..-. �;,^ ✓��;,.
<br /> .b'N,!.-,,SL'. ..rc.' M&_ � �„ _" :{r;ic,�,...,;':.�' `^�,.._ 4'.;✓;�...a�..W.,,'.,., HN�.:a'h�'
<br /> Design Conditions
<br /> Outdoor design DB: 40.0°F Heat loss: 28704 Btuh Entering coil DB: 69.5°F
<br /> Indoor design DB: 70-0°F
<br /> Manufacturer's Performance Data at Actual Design Conditions
<br /> Equipment type: Split ASHP
<br /> Manufacturer: Carrier Model: CH14NB042****A+FB4CNP042
<br /> Actual airflow: 1367 cfm ,
<br /> Output capacity: 37299 Btuh 130%of load Capacity balance: 33 OF
<br /> Supplemental heat required: 0 Btuh Economic balance: -99 OF
<br /> Backup equipment type: Elec strip
<br /> Manufacturer: Model:
<br /> Actual airflow: 1367 cfm
<br /> Output capacity: 8.6 kW 102% of load. Temp. rise: 18 OF
<br /> Meets are all requirements of ACCA Manual S.
<br /> ti �.i i71E$O 2018•Aug-31 10:54:31
<br /> 'A=ACC "( .. g Right-Suite@ Universal 2017 17A.21 RSU25554..press homesiHayden 4EHS 2605-2 N
<br /> nd tl block,rup, Cale=MJ8 House Front faces:NW Page 1