Laserfiche WebLink
i <br /> Single Family Dwelling <br /> Plan Review Comments <br /> 1. F.F.E. shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be.graded to comply with R401.3 of the F.B.C. <br /> 3. Compaction test required if 24" or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.-O.M. use permit. All 4 sides of driveway thru the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met. <br /> 7. All property markers shall be uncovered and marked at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric, plumbing, rneclianical, or framing shall be covered without an inspection and <br /> approval first: <br /> 10. All Garages shall comply with section R302,6 of the F.B.C._(Fire Separation). <br /> I L. Appliances shall not be installed in a location where subject to mechanical damage unless <br /> protected by approved barriers. M303.4 of the F.B.0 <br /> 12. Water heaters shall comply with section P607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M13.08.1 <br /> 14. Return air in all bedrooms. F.B.C. M1620.4 <br /> 15. Smoke detectors are to be installed in accordance with R313.1 of the F.B.C. <br /> 16. All glazing requirements are to be in accordance with R308.4.of the_R.B.C. <br /> 17. All means of egress are to be in accordance with R3l l of the F.B.C. <br /> 18. "Green gypsum board"shall riot be used as a backer iri showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all locations requiring an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil=burning heating <br /> .or appliances or an attached garage: They shall be;installed in accordance with the F.B.C. <br /> 21. All plumbing,mechani cal,.and electrical shall be separate from unit to unit. This includes all <br /> underground plumbing and electric. <br /> 22. Ali 2616 N.E.C. Codes will be enforced. <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11 of the 2016 N.E.0 <br /> 24. In accordance With the Land Development Code, lots shall be sodded before final at least 10 <br /> feet around the structure. <br /> 25. Blower door test and blown in insulation card shall be provided before C.O. <br /> 26. A copy of the energy eacls shall be with permit at all times. <br /> 27.. Copy of final insulation retort shall be.:provided with permit before.fnaL <br /> 28:No AMce,.pool or screen enclosure is:issued with this permit. <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C- Florida Building Code 6 h Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />