+� wrightsoft® <br /> Manual S Compliance Report Date: <br /> Entire House By: <br /> Progressive Air Systems, Inc Plan: Cali 1828 <br /> 5907 Dasher Ct,Port Richey,FL 34668 Phone:727-847-3898 Fax:727-815-3399 License:CAC033669 <br /> Project • • <br /> For: DR Horton <br /> Lot 14 Blk 11 Silverado, Zephyrhills, FL <br /> Cooling, Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.2°F Sensible gain: 20893 Btuh Entering coil DB: 75.4°F <br /> Outdoor design WB: 77.1 OF Latent gain: 2966 Btuh Entering coil WB: 62.7°F <br /> Indoor design DB: 75.0°F Total gain: 23859 Btuh <br /> Indoor RH: 50% Estimated airflow: 1000 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Carrier Model: CH14NB030+FB4CNP030 <br /> Actual airflow: 1000 cfm <br /> Sensible capacity: 23272 Btuh 111%of load <br /> Latent capacity: 3908 Btuh 132%of load <br /> Total capacity: 27180 Btuh 114%of load SHR: 86% <br /> Heating 'equipment <br /> Design Conditions <br /> Outdoor design DB: 40.0°F Heat loss: 21100 Btuh Entering coil DB: 69.8°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Carrier Model: CH14NB030+FB4CNP030 <br /> Actual airflow: 1000 cfm <br /> Output capacity: 25604 Btuh 121%of load Capacity balance: 32 OF <br /> Supplemental heat required: 0 Btuh Economic balance: -99 OF <br /> Backup equipment type: . Elec strip <br /> Manufacturer: Model: <br /> Actual airflow: 1000 cfm <br /> Output capacity: 6.6 kW 107%of load Temp. rise: 20 OF <br /> Meets are all requirements of ACCA Manual S. <br /> 4� wri htsoft° 2018-Nov-0615:33:26 <br /> �� 9 Right-Suite®Universal 2017 17.0.21 RSU25554..ightsoft Files\Express homes\Cali 4EBB 1828.rup Calc=MJ8 House Front faces: W Page 1 <br />