Xenon flashtdbe enclosed in a rugged Lexan®lens. The shall be able to be synchronized on a 2-wire circuit with ,
<br /> strobes shall be available with two or four field select- the capability to silence the audible if required. If the
<br /> able settings in one unit and shall be rated, per UL 1971, sync module or power supply fails to operate (i.e., con-
<br /> for up to 185 cd for wall mounting and 177 cd for ceiling tacts remain closed), the strobes shall revert to a non-
<br /> mounting. The strobes shall operate over an extended synchronized flash rate. All notification appliances shall
<br /> temperature range of 32°F to 120°F (0°C to 49°C) and be listed for"Special Applications".
<br /> be listed for maximum humidity of 95% RH. Strobe • Strobes are designed to flash at 1 flash per second
<br /> inputs shall be polarized for compatibility with standard minimum over their"Regulated Input Voltage Range".
<br /> reverse polarity supervision of circuit wiring by a Fire
<br /> Alarm Control Panel (FACP). • All candela ratings represent minimum effective strobe
<br /> Audibles and Audible/Strobe Combinations intensity based on UL Standard 1971.
<br /> • Series ZH Strobe products are listed under UL Stan-
<br /> Horns and horn/strobes shall be listed for Indoor use un- dards 1971 and 464 for indoor use with a temperature
<br /> der UL Standard 464. The horns shall be able to produce range of 32°F to 120OF (0°C to 49°C) and maximum
<br /> a continuous output or a temporal code-3 output that can humidity of 93% (±2%).
<br /> be synchronized. The horns shall have at least 2 sound
<br /> level settings of 90 and 95 dBA. Series ZH horns are listed under UL Standard 464 for
<br /> Synchronization Modules
<br /> audible signal appliances (indoor use only).
<br /> When synchronization of strobes or temporal Code-3 au- Technical Information
<br /> dibles is required, the appliances shall be synchronized
<br /> using the Siemens DSC sync modules, FS-250 panels, For complete technical information, please consult the
<br /> XLS panels, or PAD-3 power suppies with built-in sync relevant installation sheets as well as the Siemens
<br /> protocol. The strobes shall not drift out of synchroniza- Compatibility Guide.
<br /> tion at any time during operation. Audibles and strobes
<br /> Ordering Information / Mounting Requirements /Approvals
<br /> Mounting Agency Approvals
<br /> Model Number Order Code Options#
<br /> UL ULC CSFM FM
<br /> ZH-MC-R 500-636161 B,D,E,F X # # #
<br /> ZH-MC-W 500-636162 B,D,E,F X # # #
<br /> ZH-HMC-R 500-636163 B,D.E,F X # # #
<br /> ZH-HMC-W 500-636164 B,D,E,F X # # #
<br /> ZH-R 500-636159 B.D,E, F X # # #
<br /> ZH-W 500-636160 B,D.E, F X # # #
<br /> ZH-MC-CR 500-636165 B.D,E.F X # # #
<br /> ZH-MC-CW 500-636166 B,D,E, F X # # #
<br /> ZH-HMC-CR 500-636167 B,D,E,F X # # #
<br /> ZH-HMC-CW 500-636168 B,D,E,F X # # #
<br /> ZR-MC-R 500-636169 B,D,E,F X # # #
<br /> ZR-MC-W 500-636170 B,D,E, F X # # #
<br /> ZR-HMC-R 500-636171 B,D,E,F X # # #
<br /> ZR-HMC-W 500-636172 B,D,E,F X # # #
<br /> ZR-MC-CW 500-636174 B,D,E, F X # # #
<br /> ZR-MC-CR 500-636173 B,D,E,F X # # #
<br /> ZR-HMC-CR 500-636175 B,D,E,F X # # #
<br /> ZRS-HMC-CW 500-636176 B,D,E,F X # # #
<br /> ZBB-R 500-636193 Accessory-Includes base,dust cover,mounting screws and installation sheet
<br /> ZBB-W 1500-636194 1Accessory-Includes base,dust cover,mounting screws and installation sheet
<br /> X=listed/approved #=pending '= Refer to Data Sheet#2585 for mounting options.
<br /> WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE
<br /> USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,
<br /> CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION
<br /> OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
<br /> SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
<br /> Fire Safety Fire Safety
<br /> 8 Fernwood Road 2 Kenview Boulevard
<br /> Florham Park,NJ 07932 7/07 Brampton,Ontario
<br /> Siemens Building Technologies Tel:(973)593-2600 5M Canada L6T 5E4
<br /> FAX:(973)593-6670 SFS-IG Tel:(905)799-9937 July 2007
<br /> Fire Safety Website:www.sbt.siemens.com/fis Printed in U.S.A. FAX:(905)799-9858 New Issue
<br />
|