Engineering Specifications Synchronization is possible when using the Siemens DSC <br /> sync modules, FS-250 panel, XLS panel, or PAD-3 power <br /> The chime appliances shall be Siemens Series CH supply with built-in sync protocol. The strobes shall not drift <br /> Chimes and the chime strobe appliances shall be Sie- out of synchronization at any time during operation. If the <br /> mens Series CH Chime Strobes or approved equals. sync module or Power Supply fails to operate, (i.e., contacts <br /> The chime shall be UL Listed under Standard 464 for remain closed), the strobe shall revert to a non-synchronized <br /> Audible Signal Appliances and chimes equipped with flash rate. <br /> strobes shall be listed under UL Standard 1971 for <br /> Emergency Devices for the Hearing-Impaired. In addi- The chime and the chime strobe appliances shall be de- <br /> tion, the strobes shall be certified to meet the require- signed for indoor surface or flush mounting. The chime and <br /> ments of FCC Part 15, Class B and shall incorporate low chime strobe shall incorporate a chime mounting plate with a <br /> temperature compensation to ensure the lowest possible grille cover which is secured with two screws for a level, fin- <br /> current consumption. ish and shall mount to standard electrical hardware requiring <br /> All chimes shall use solid state components and shall no additional trimplate or adapter. <br /> provide field selectable single stroke or vibrating opera- All notification appliances shall be listed for"Special Applica- <br /> tion with volume control and tone control.All models tions". <br /> shall have a peak anechoic sound output of 83 dB at 10 General Notes: <br /> feet and an adjustable frequency range of 800 to 1200 <br /> Hz.All inputs shall employ terminals that accept#12 to Strobes are designed to flash at 1 flash per second mini- <br /> #18 AWG wire sizes. mum over their"Regulated Input Voltage Range". Note <br /> The strobe portion of the appliance shall produce a flash that NFPA-72 specifies a flash rate of 1 to 2 flashes per <br /> rate of one (1)flash per second over the Regulated second and ADA Guidelines specify a flash rate of 1 to 3 <br /> Input Voltage Range and shall incorporate a Xenon flashes per second. <br /> flashtube enclosed in a rugged Lexan®lens. The strobe All candela ratings represent minimum effective Strobe <br /> shall be of low current design. Where Multi-Candela intensity based on UL Standard 1971. <br /> Chime Strobes are specified,the strobe intensity shall <br /> have field selectable settings and shall be rated per UL <br /> Standard 1971 at: 15/30/75/110cd for wall mount and Technical Information: <br /> 15/30/75/95cd or 115/177cd for ceiling mount. The selec- <br /> tor switch for selecting the candela shall be tamper resis- For complete technical information, please consult the rel- <br /> tant and not accessible from the front of the appliance. evant installation sheets as well as the Siemens Compatibility <br /> Guide. <br /> Ordering Information / Mounting Requirements /Approvals <br /> Model Number Order Code <br /> Mounting Agency Approvals <br /> Options— UL UCL CSFM FM <br /> CH-MC-R 500-636017 PQ,R,U,Y X # # # <br /> CH-MC-W 500-636018 PQ,R,U,Y X # # # <br /> CH-MC-CR 500-636021 Q,U X # # # <br /> CH-MC-CW 500-636022 Q,U X # # # <br /> CH-HMC-CW 500-636023 Q,U X # # # <br /> CH-R 500-636019 PQ,R,U,Y X # # # <br /> CH-W 500-636020 PQ,R,U,Y X # # # <br /> CH-CW 500-636024 Q,U X # # # <br /> X= listed/approved #= pending *= Refer to Data Sheet#2585 for mounting options. <br /> WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE <br /> USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, <br /> CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION <br /> OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND <br /> SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. <br /> Fire Safety Fire Safety <br /> 8 Fernwood Road 2 Kenview Boulevard <br /> Florham Park,NJ 07932 7/07 Brampton,Ontario <br /> Tel:(973)593-2600 5M Canada L6T 5E4 <br /> Siemens Building Technologies <br /> FAX:(973)593-6670 SFS-IG Tel:(905)799-9937 July 2007 <br /> Fire Safety Website:www.sbt.siemens.com/fis Printed in U.S.A. FAX:(905)799-9858 New Issue <br />