1 <br /> 1 <br /> Project:FMC <br /> Title: Florida Medical Clinic <br /> Type: Office <br /> (WEA File:FL_TAMPA_INTERNATIONAL 'AP.tm3) <br /> Building End Uses <br /> 1)Proposed 2)Baseline <br /> Total 1,409.90 1,845.80 <br /> $21,894 $28,827 <br /> ELECTRIC ITY(MBtulkWh/$) 1,409.90 1,845.80 <br /> 413094 540842 <br /> $21,$94 $28,827. <br /> AREA LIGHTS 337:90 362.90 <br /> 99008 106338 <br /> $5,247 $5,668 <br /> MISC EQUIPMT 469.30. 469.30 . <br /> 137506 137506 <br /> .$7,288 $7,329 <br /> PUMPS&MISC 0.10 0.00 <br /> 17 11 <br /> $1 $1 <br /> SPACE COOL 454.40 547.90 <br /> 133131 160532 <br /> $7,056 $8,556 <br /> SPACE HEAT 1.30 . .. 3.60 .. <br /> 394 1051 <br /> $21 $56 . <br /> VENT FANS 146.90 462.10 <br /> 43038 135404 <br /> $2,281- $7,217 <br /> Credits Applied: None PASSES <br /> Passing Criteria=24503 <br /> Design (including'any credits)=21894 <br /> Passing requires Proposed Building cost to be at most 85% of <br /> Baseline cost.This Proposed Building is 'at 75.9% <br /> Energy0auge Summit@ Fla/Com=2017.TAM 2017-1.0 Compliant Software.Effective Date: Dec.31,2017 <br /> Florida Building Code,Sixth Edition(2017)-Energy.Conservation IECC 2015-Total Building Performance Compliance Option <br /> 2/13/2018 Page 5 of 25 <br />