Laserfiche WebLink
Page 16 of 20 TFP1020 <br /> that it will not cause accidental dam- <br /> Installation age to property or danger to persons. valve Setting <br /> NOTES Step 7.Unused pressure alarm switch procedure <br /> Proper operation of the Model DPV-1 and/or water motor alarm connections <br /> Dry Pipe Valve depends upon its trim must be plugged. Steps 1 through 11 are to be per- <br /> being installed in accordance with the Step 8.The Pressure Relief Valve pro- formed when initially setting the Model <br /> instructions given in this Technical vided with the Valve Trim is factory set DPV-1 Dry Pipe Valve;after an opera- <br /> Data Sheet. Failure to follow the ap- to relieve at a pressure of approxi- tional test of the fire protection system; <br /> propriate trim diagram may prevent mately 45 psi(3,1 bar),which can typi- or,after system operation due to a fire. <br /> the DPV-1 Valve from functioning cally be used for a maximum normal <br /> properly, as well as void listings, ap- system air pressure of 40 psi(2,8 bar). NOTES <br /> provals, and the manufacturer's war- The Pressure Relief Valve may be re- If the DPV-1 is equipped with a Dry <br /> ranties. set to a lower or higher pressure;how- Pipe Valve Accelerator, refer to its re- <br /> Failure to latch open the Clapper As- ever,it must be be reset to relieve at a setting instructions before resetting <br /> sembly prior to a system hydrostatic pressure which is in accordance with the DPV-1. Refer to TFP1100 for the <br /> test may result in damage to the Clap- the requirements of the Authority Hav- QRS or TFP1112 for the ACC-1. <br /> per Assembly. ing Jurisdiction. Based on the instructions provided,re- <br /> The DPV-1 Valve must be installed in To reset the Pressure Relief Valve, set the Accelerator at the appropriate <br /> a readily visible and accessible loca- first loosen the jam nut and then adjust time during the resetting of the DPV-1. <br /> tion. the cap accordingly—clockwise for a Step 1.Close the Main Control Valve, <br /> higher pressure setting or counter- and close the Air Supply Control Valve <br /> The DPV-1 Valve and associated trim clockwise for a lower pressure setting. (Fig. 4, 5, or 6). If the DPV-1 is <br /> must be maintained at minimum tem- After verifying the desired pressure equipped with a Dry Pipe Valve Accel- <br /> perature of 40 F14 C. setting,tighten the jam nut. erator,remove the Dry Pipe Valve Ac- <br /> Heat tracing of the DPV-1 Valve or its Step 9. Installation of an Air Mainte- celerator from service in accordance <br /> associated trim is not permitted. Heat nance Device, as described in the with its Technical,Data Sheet(Refer to <br /> tracing can result in the formation of Technical Data Section, is recom- TFP1100 for the°QRS or TFP1112 for <br /> hardened mineral deposits that are ca- mended. the ACC-1). <br /> pable of preventing proper operation. Step 10.An Inspector's Test Connec- Step 2. Open the Main Drain Valve <br /> The Model DPV-1 Dry Pipe Valve is to tion as required By NFPA 13 must be (Fig.4,5,or 6)and all auxiliary drains <br /> be installed in accordance with the fol- provided on the system piping at the in the system.Close the auxiliary drain <br /> lowing criteria: most remote location from the Model valves after water ceases to dis- <br /> Step 1. All nipples, fittings, and de- DPV-1 Valve. charge. Leave the Main Drain Valve <br /> vices must be clean and free of scale Step 11. Conduit and electrical con- open. <br /> and burrs before installation. Use pipe nections are to be made in accordance Step 3. Depress the plunger of the <br /> thread sealant sparingly on male pipe with the requirements of the authority Automatic Drain Valve(Fig.4,5, or 6) <br /> threads only. having jurisdiction and/or the National to verify that it is open and that the <br /> Step 2. The DPV-1 Valve must be Electric Code. DPV-1 Valve is completely drained. <br /> trimmed in accordance with Figures 4, Step 12. Before a system hydrostatic Step 4.Open the Optional Alarm Con- <br /> 5, or 6, as applicable. If the DPV-1 is test is performed in accordance with trol Valve (Fig. 4, 5, or 6), as applica- <br /> to be equipped with a Dry Pipe Valve NFPA 13 system acceptance test re- ble, if it was closed to silence local <br /> Accelerator, refer to the Technical quirements, the Clapper Assembly is alarms. <br /> Data Sheet TFP1100 for the Model to be manually latched open(Ref. Fig. Step 5. As necessary, replace all <br /> QRS Electronic Dry Pipe Valve Accel- 3D);the Automatic Drain Valve(Fig.4, sprinklers that have operated. Re- <br /> erator or TFP1112 for the Model ACC- 5, or 6) is to be temporarily replaced placement sprinklers must be of the <br /> 1 Mechanical Dry Pipe Valve Accel- with a 1/2 inch NPT plug,the 3/32 inch same type and temperature rating as <br /> erator. Vent Fitting (Item 13, Fig. 4; Item 15, those which have operated. <br /> Step 3. Care.must be taken to make Fig. 5; or Item 15, Fig. 6) is to be <br /> sure that check valves, strainers, temporarily replaced with a 1/4 inch NOTE <br /> globe valves,etc.are installed with the NPT plug, and the Handhole Cover In order to prevent the possibility of a <br /> flow arrows in the proper direction. Bolts are to be tightened using a cross- subsequent operation of an over- <br /> draw sequence. heated solder type sprinkler, any sol- <br /> Step 4. Drain tubing to the drip funnel der type sprinklers which were possi- <br /> must be installed with smooth bends bly exposed to a temperature greater <br /> that will not restrict flow. than their maximum rated ambient <br /> Step 5.The main drain and drip funnel must be replaced. <br /> drain may be interconnected provided Step 6.Push down on the Reset Knob <br /> a check valve is located at least 12 (Fig. 3E)to allow the Clapper Assem- <br /> inches(300 mm)below the drip funnel. bly to reseat. <br /> The Low Body Drain Valve (Fig. 4, 5, <br /> or 6) may be piped so as to discharge Step 7. Pressurize the system with air <br /> into the Drip Funnel or to a separate (or nitrogen) to 10 psi (0,7 bar), and <br /> drain. then individually open all auxiliary <br /> Step 6. Suitable provision must be drain valves in the system piping to <br /> made for disposal of drain water. <br /> drain any remaining water in trapped <br /> sections. Close each drain valve as <br /> Drainage water must be directed such soon as water ceases to discharge. <br />