Laserfiche WebLink
Pressure / Flow Summary - STANDARD <br /> Beneficial Fire Protection Page 4 <br /> FMC ZEPHYRHILLS EAST PORTE COCHERE Date 070518 <br /> Node Elevation K-Fact Pt Pn Flow Density Area Press <br /> No. Actual Actual Reg. <br /> D001 11.5 5.6 12.13 na 19.5 0.15 130 7.0 <br /> D002 11.5 5.6 12.13 na 19.5 0.15 130 7.0 <br /> 4C 17.5 K=K @ EQ01 22.35 na 22.01 <br /> 4F 17.5 K=K @ EQ01 22.44 na 22.06 <br /> 41 17.5 K=K @ EQ01 22.87 na 22.26 <br /> 4L 17.5 K=K @ EQ01 23.6 na 22.62 <br /> 4M 15.17 K=K @ EQ01 21.0 na 21•.34 <br /> 4N 15.17 K=K @ EQ01 22.33 na 22.0 <br /> 40 15.17 K=K @ EQ01 22.33 na 22.0 <br /> 4A 17.5 K=K @ EQ01 17.54 na 19.5 <br /> 413 17.5 K=K @ EQ02 18.95 na 20.06 <br /> 4D 17.5 K=K @ EQ01 17.62 na 19.54 <br /> 4E 17.5 K=K @ E002 19.03 na 20.1 <br /> 4G 17.5 K=K @ EQ01 17.95 na 19.73 <br /> 4H 17.5 K=K @ EQ02 19.39 na 20.29 <br /> 4J 17.5 K=K @ EQ01 18.54 na 20.05 <br /> 4K 17.5 K=K @ EQ02 20.02 na 20.62 <br /> 18 15.17 22.58 na <br /> 19 15.17 24.0 na <br /> 60 17.5 23.97 na <br /> 61 17.5 24.07 na <br /> 62 17.5 24.52 na <br /> 63 17.5 25.3 na <br /> 64 15.17 33.98 na <br /> 65 12.17 39.43 na <br /> DTOR 12.17 40.39 na <br /> DBOR 3.0 46.7 na <br /> BOR -3.0 49.74 na <br /> BFD 3.0 48.04 na <br /> BFS -3.0 53.58 na <br /> SRCE 0.0 52.52 na 250.0 <br /> The maximum velocity is 24.26 and it occurs in the pipe between nodes 19 and 64 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />