Laserfiche WebLink
� a <br /> Manual S Compliance Report Job: 2277B sf ADS Carder= <br /> Date: 3/7/2019 <br /> Entire House By: Dave Aldrich <br /> Bayonet Plumbing Heating and Cooling <br /> 8950 New York ave,Hudson <br /> Project • • <br /> For: Lennar Homes <br /> Gooling Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.3°F Sensible gain: 27068 Btuh Entering coil DB: 75.5°F <br /> Outdoor design WB: 77.3°F Latent gain: 3736 Btuh Entering coil WB: 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 30804 Btuh <br /> Indoor RH: 50% Estimated airflow: 1200 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: SplitASHP <br /> Manufacturer: Carrier Model: 25HBC537A0030+FX4DNF037L <br /> Actual airflow: 1200 cfm <br /> Sensible capacity: 29750 Btuh 110% of load <br /> Latent capacity: 5250 Btuh 141%.of load <br /> Total capacity: 35000 Btuh 114% of load SHR: 85% <br /> Heating'5quipmentu <br /> Design Conditions <br /> Outdoor design DB: 30.8°F Heat loss: 29648 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Carrier Model: 25HBC537A0030+FX4DNF037L <br /> Actual airflow: 1200 cfm <br /> Output capacity: 26719 Btuh 90% of load Capacity balance: 29 °F <br /> Supplemental heat required: 2929 Btuh Economic balance: -99 °F <br /> Backup equipment type: Elec strip <br /> Manufacturer: n/a Model: n/a+n/a <br /> Actual airflow: 1200 cfm <br /> Output capacity: 0 kW 0% of load Temp. rise: 0 °F <br /> Meets all requirements of ACCA Manual S. <br /> ' Wrightsofta 2019-Mar-0714:40:06 <br /> aaR�aak 4ow����mN Right-Suite®Universal 2018 18.0.16 RSU05714 Page 1 <br /> ...sf ADS Tampa ONLY template VW 3 ton Carrier.rup Calc=MJ8 Front Door faces:SE <br />