Laserfiche WebLink
External Lighting Compliance <br /> Description Category Tradable? Allowance Area or Length ELPA CLP <br /> (W/Unit) or No.of Units (W) (VV) <br /> (Sgft or ft) <br /> None <br /> Project:Pizza Hut <br /> Title:Pizza Hut <br /> Type:Dining:Family <br /> (WEAFile:FL_TA IPA INTERNATIONAL AP.tm3) <br /> Lighting Power Compliance <br /> Space Ashrae Description Area Height No.of Design Effective Allowance <br /> ID (sq.ft) (ft) Spaces (W) (W) (Vi) <br /> Lobby 12 Lobby(General)- 323 10.0 1 209 209 342 <br /> Reception and Waiting <br /> Restroom 6 Toilet and Washroom 82 12.0 1 45 45 80 <br /> Kitchen 7 Food Service-Kitchen 1,423 9.3 1 851 851 1,722 <br /> Design 1104(W) PASSES <br /> Effective: 1104(W) <br /> Allowance: 2144.57(W) <br /> Passing requires Design to be at most 100%of Criteria <br /> Project:Pizza Hut <br /> Title:Pizza Hut <br /> Type:Dining:Family <br /> (WEA File:FL TAMPA_INTERNATIONAL AP.tm3) <br /> Lighting Controls Compliance <br /> Acronym Ashrae Description Area Design Min Compli- <br /> ID (sq.ft) CP CP ance <br /> Lobby 12 Lobby(General)-Reception and 323 3 1 PASSES <br /> Waiting <br /> Restroom 6 Toilet and Washroom 82 1 1 PASSES <br /> Kitchen 7 Food Service-Kitchen 1,423 2 1 PASSES <br /> PASSES <br /> EnergyGauge Summit®Fla/Com-2017.TAM 2017-1.0 Compliant Software.Effective Date: Dec 31,2017 <br /> Florida Building Code,Sixth Edition(2017)-Energy Conservation ASHRAE 90.1-2013-Prescriptive Compliance Option <br /> 7/6/2018 Page 5 of 21 <br />