My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
18-20615
Zephyrhills
>
Building Department
>
Permits
>
2018
>
18-20615
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/13/2020 1:59:41 PM
Creation date
1/13/2020 1:59:40 PM
Metadata
Fields
Template:
Building Department
Company Name
HIDDEN RIVER
Building Department - Doc Type
Permit
Permit #
18-20615
Building Department - Name
LENNAR HOMES LLC
Address
2972 MOULDEN HOLLOW DR
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
14
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Single Family Dwelling <br /> Plan Review Comments <br /> 1: F.F.E. shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to comply with R401.3 of the F.B.C. <br /> 3. . Compaction test required:if 24"or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5: Driveways require a R.O.W. use permit. All 4 sides of.driveway thru the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met. <br /> 7. All property markers shall be uncovered and marked at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric,plumbing, mechanical; or framing shall be-covered without an inspection and <br /> approval first. <br /> 10. All Garages-shall,comply with section R302.6 of the F.B.C. (Fire Separation). <br /> 11.Appliances shall not be installed in a location where subject to mechanical damage unless <br /> protected by approved barriers. M303.4 of the F.B.C. <br /> 12. Water heaters shall comply with section P607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M13.08.1 <br /> 14. Return air in,all bedrooms. F.B.C. M.1620A <br /> 15. Smoke detectors are to be 'installed in accordance with R313.1 of the.RB.C. <br /> 16. All glazing requirements are to be in accordance with R308.4 of the F.B.C-. <br /> 17. All means of egress are to be in accordance with R31;1 of the RB.C. <br /> 18: "Green gypsum board"shall not be used as a backer.in showers or tubs. R702.4,2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all locations requiring an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in new construction that use fossil-burning heating <br /> or appliances or an attached garage. They shall be installed in accordance with the F.B.C. <br /> 21. All plumbing,mechanical, and electrical shall be separate from unit to:unit. This includes all <br /> underground plumbing and electric. <br /> 22. All 2616 N.-E.C. Codes will be enforced. <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11 of the 2016 N.E.-C <br /> 24. In accordance with.the Land Development Code, lots shall be sodded before final at least 10 <br /> feet around the structure. <br /> 25. Blower door test and blown in insulation card shall be provided before C.O. <br /> 26.A coax of the energy eacls shall be with permit at-all times. <br /> 27. Covy of findl insulation report shall be.:provided with:permit before:rinal <br /> 28.No fence,.pool or screen-enclosure is:issued with this permit. <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C- Florida Building Code 6 h Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />
The URL can be used to link to this page
Your browser does not support the video tag.