DONNELLY ENGINEERING ELECTRICAL <br /> SECTION 16110 <br /> RACEWAYS AND CONDUIT <br /> PART 1 -GENERAL <br /> 1.1 RELATED DOCUMENTS <br /> A. General: Drawings and general provisions of the Contract, including General and Supplementary <br /> Conditions and Division 1 Specification sections, apply to work of this section. <br /> 1.2 DESCRIPTION <br /> A. General: Provide all supports, hangers and inserts required to mount conduit, pullboxes and other <br /> equipment provided under this Division. <br /> B. Support: All items shall be supported from the structural portion of the project where applicable. Supports <br /> and hangers shall be of a type listed by Underwriters' Laboratories. Wire shall not be used as a support. <br /> Boxes and conduit shall not be supported or fastened to ceiling suspension wires or to ceiling channels. Do <br /> not install any devices supported by ceiling tiles. <br /> C. Installation: The Contractor shall lay out and provide their work in advance of the any construction of floors <br /> or walls, and shall provide all sleeves that may be required for openings through floors, walls, etc. Where <br /> plans call for conduit to be run exposed, provide all inserts and clamps for the supporting of conduit. <br /> D. Systems: Provide conduit system of empty raceways including terminal cabinets, backboards and outlets <br /> as described and specified herein. <br /> 1.3 QUALITY ASSURANCE <br /> A. Qualifications: Manufacturers shall be regularly engaged in the manufacture of conduit systems and <br /> fittings of types and sizes required, and whose products have been in satisfactory use in similar service for <br /> not less than 5 years in the USA. <br /> B. Compliance: Materials shall comply with the latest edition of the following standards as they apply to the <br /> different raceway types specified herein; <br /> 1. ANSI: <br /> a. ANSI C80.1: Rigid Steel Conduit(RSC) <br /> b. ANSI C80.3: Electrical Metallic Tubing (EMT) <br /> 2. UL: <br /> a. UL 1: Flexible Metal Conduit <br /> b. UL 6: Rigid Steel Conduit(RSC) <br /> C. UL 360: Liquid-Tight Flexible Metal Conduit <br /> d. UL 514: Fittings for Metal Conduit <br /> e. UL 797: Electrical Metallic Tubing (EMT) <br /> f. UL 1242: Intermediate Metal Conduit(IMC) <br /> 3. NEMA: <br /> a. NEMA TC3: Fittings for Rigid Nonmetallic Conduit(RNMC) <br /> b. NEMA RN1: Plastic Coated Metal Conduit <br /> 4. Federal Specifications: <br /> a. WW-C-581: Rigid Steel Conduit(RSC) <br /> b. WW-C-563: Electrical Metallic Conduit(EMT) <br /> C. WW-C-566: Flexible Steel Conduit <br /> d. WW-C-581 E: Intermediate Metallic Conduit(IMC) <br /> e. WC-582A Conduit, Raceway, Metal and Fittings <br /> Heartland Health Care Center of Zephyrhills-3181 16110-1 DE No 217032 <br /> 38220 Henry Drive,Zephyrhills, FL 33542 Pending Emergency Rule 59A-4.1265 <br />