Laserfiche WebLink
Manual S Compliance Report Job: 3246A sf ADS CarrierDate: 9118/2018 <br /> lower floor By: Dave Aldrich <br /> Bayonet Plumbing Heating and Cooling <br /> 8950 New York ave,Hudson <br /> i <br /> Project • • <br /> For: Lennar Homes <br /> Cooling Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.4°F Sensible gain: 20159 Btuh Entering coil DB: 75.6°F <br /> Outdoor design WB: 77.2°F Latent gain: 1748 Btuh Entering coil WB: 62.8°F <br /> Indoor design DB: 75.0°F Total gain: 21907 Btuh <br /> Indoor RH: 50% Estimated airflow: 800 cfm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Carrier Model: 25HBC524A00300+FB4CNP025L <br /> Actual airflow: 800 cfm <br /> Sensible capacity: 20400 Btuh 101% of load <br /> Latent capacity: 3600 Btuh 206% of load <br /> Total capacity: 24000 Btuh 110% of load SHR: 85% <br /> Heating Equipment <br /> Design Conditions <br /> Outdoor design DB: 32.1 OF Heat loss: 25732 Btuh Entering coil DB: 69.6°F <br /> Indoor design DB: 70.0°F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipment type: Split ASHP <br /> Manufacturer: Carrier Model: 25HBC524A00300+FB4CNP025L <br /> Actual airflow: 800 cfm <br /> Output capacity: 18859 Btuh 73% of load Capacity balance: 35 OF <br /> Supplemental heat required: 6873 Btuh Economic balance: -99 OF <br /> i <br /> Backup equipment type: Elec strip <br /> Manufacturer: Model: <br /> Actual airflow: 800 cfm <br /> Output capacity: 7.1 kW 94% of load Temp. rise: 50 OF <br /> Meets all requirements of ACCA Manual S. <br /> - wrightsoft- 2018-Sep-18 07:14:10 <br /> Right-Suite®Universal 2018 18.0.16 RSU05714 Page 1 <br /> ACCK ...pment\3246 sf ADS template 2,2 ton Carrier.rup Cale=MJ8 Front Door faces:SW <br />