Laserfiche WebLink
i <br /> I <br /> Single Family Dwelling <br /> Plan Review Comments <br /> I ' <br /> 1: F.F.E. shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to comply with R40.1.3 of the RB.C. <br /> 3. Compaction test required if,2.4"or more of fill dirt.is brought in at any one place. <br /> 4. Tie in' survey required before pouring concrete. <br /> 5. Driveways require a R.O.W. use permit. All 4 sides of driveway thm the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met: <br /> 7. All property markers shall be uncovered and marked at time of first inspectio_n. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric, plumbing, mechanical, or framing shall be.covered without an inspection and <br /> approval first. <br /> 10. All. Garages shall comply with section R302..6 of the F.B.C.-(Fire Separation). <br /> 11._ Appliances shall not be installed_ in a location where subject to mechanical damage unless <br /> protected by approved.barriers. M303.4 of the F.B.0 <br /> 12. Water heaters shall comply with section.P607,3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M13.08.1 <br /> 14. Return air in all bedrooms. F.B.C. M.1620.4 <br /> 15. Smoke detectors are to be installed in accordance with R313..1 of the F.B.C. <br /> 16. All glazing requirements are to be in accordance with R308.4.of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311 of the RB,C. <br /> 18. "Green gypsum board"shall not be used as a backer in showers or tubs. R702.4.2 F.B,C. <br /> 19. Combination-type AFCI breakers are required at all locations requiring an AFCI'type breaker: <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil.=burning heating <br /> or appliances or an attached garage. They shall be installed in accordance with the F.B.C. <br /> 21. All plumbing,mechanical, and electrical shall_ be separate from unit to unit. This includes all <br /> underground plumbing and electric. <br /> 22. All 2016 N.E.C. Codes will be enforced. <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11,of the 2016 N.E.0 <br /> 24: In accordance with the Land Development Code, lots shall be sodded before final at least 10 <br /> feet around the structure: <br /> 25. Blower door test and blown in insulation-card shall be provided before C:O. <br /> 26. A copy of the energy eacls shall be with permit at all times. <br /> 27.. Copy of final insulation report shall be:provided with:permit before.LnaL <br /> 28: No fence;:pool or screen enclosure -is'issued with-this permit <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C- Florida Building Code 6"'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />