Laserfiche WebLink
i <br /> Single Family Dwelling <br /> Plan Review Comments <br /> 1. F.F.E. shall be a minimum of.8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to comply with R401.3 of the F.B.C. <br /> 3. Co* action test required if_24" or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5. Driveways require a R:O.W. use permit. All 4.sides of driveway thru the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met. <br /> 7. All property markers shall be uncovered and marked at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric, plumbing, mechanical; or framing shall be covered without an:inspection and <br /> approval first. <br /> 10. All Garages shall comply with section R302.,6 of the F.B.C. (Fire Separation). <br /> I I, Appliances shall not be installed in a location where subject to mechanical damage unless <br /> protected by approved_barriers. M303.4.of the F.B:C <br /> 12. Water heaters shall comply with section P607.3 of the F:B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M1308.1 <br /> 14. Return air in all bedrooms: F.B.C. M.1620.4 <br /> 15. Smoke detectors are to be installed in accordance with R313.1 of the F.B.C. <br /> 16. All glazing requirements are to be in accordance with R308.4 of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311 of the F.B.C., <br /> 18. "Green gypsum board" shall not b' used ' a backer.in-showers or tubs. R702.4:2 F.B.C. <br /> . . . . <br /> 19. Combindtion-type AFCI breakers are required at all locations requiring an AFCI:type breaker. <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil=burning heating <br /> or appliances or an attached pp garage: They shall be installed in accordance with the F.B.C. <br /> 21. All plumbing,mechanical, and electrical shall be separate from unit_to:unit. This includes all <br /> underground_plumbing and electric. <br /> 22. All 2016 N.E.C; Codes will be enforced. <br /> -23. Tamper- Resistant Rec septacle m accordance with 406.11 of the 2016 N.E.0 <br /> 24. In accordance with the Land Development Code, lots shall_ be sodded before final-at.least 10 <br /> feet around the structure. f <br /> 25. Blower door test and blown in insulation card shall be provided before C.O. <br /> 26.. A copy of the energy cacls shall be with permit at.all times j <br /> 27.. Copy,of findl insulation report shall he.:proyided with:permit before:tinaL <br /> 28.No fence: pool-or screen_enelosure is issued with this oermirk. <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-Florida Building Code 60'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />