Laserfiche WebLink
Single Family Dwelling <br /> Plan Review Comments <br /> 1: F.F.E:.shall be a minimum of 8 above the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to comply with R401.3-of the F.B.C. <br /> I Compaction test required if.24"or more of fill dirt.is brought in at any one place. <br /> 4. Tie in survey required before pouring.concrete. <br /> 5. Driveways require a R:O:W. use permit. A11.4 sides of driveway thru the sidewalk shall-Have <br /> expansion material. <br /> 6. All setbacks shall be met: <br /> 7. All.property markers shall be uncovered and marked.at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric,plumbing,mechanical; or fratriirig shall be covered without an inspection and <br /> approval first: <br /> 10. All Garages shall comply with.section R3016 of the F.B.C..(Fire Separation). <br /> 11. Appliances shall not be installed in a locationwhere subject to mechanical damage unless <br /> protected by approved barriers. M303.4:of the F.B.0 <br /> 12. Wate'r.heaters shall comply with section P607,3 of the F.R.C. <br /> 13.Foundation supports for A/C units shall be raised at least 3" above finished grade. M130.8.1 <br /> 14. Return air.in all bedrooms. F.B.C. M.1620.4 <br /> 15. Smoke detectors are to be installed in accordance with R31-3.1 of the F.B.C. <br /> 16, All.glazing requirements are to be in accordance'with R308:4-of the F.B.C. <br /> 17.All means of egress are,to,be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board shall riot be used-as a backer in:showers or tubs. R702.4:2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all locations requiring'an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in.riew.construction that uses fossil-burning heating <br /> or appliances or an attached garage; They shall be installed in accordance with the F.B.C; <br /> 21. All plumbing, mechanical, and.electrical shall be separate from unit.to.unit: This includes all. <br /> underground plumbing and electric. <br /> 22.. A112016 N.E.Q. Codes will be enforced: <br /> 23. Tairiper= Resistant Receptacles in accordance with 406.11 of the 2016 NEC <br /> 24: In accordance with the Land Development.Code,-lots shall be sodded before final.at least 10 <br /> feet around the structure: <br /> `25.Blower door test shall be provided before.C.O. <br /> 26.A cotes Of ever y eacls shall be with-Hermit at-all times. <br /> 27 Cotiy of final insulation,report shall be.:provided with:permit before:r1naL <br /> 28:No fence,:Hoo[6r screen enclosaie is:issued with-this permit <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-Florida Building Code 6fl'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br /> 1 <br />