Laserfiche WebLink
Single Family Dwelling <br /> Plan Review Comments <br /> 1: F.F.E..shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be.graded to comply with R401.3 of the F.B.C. <br /> 3... Compaction test required if 2.4" or more of fill dirt is brought in at any one place. <br /> 4, Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.O.W. use permit. All 4 sides of driveway thru'the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met: <br /> 7. All.property markers shall be uncovered and marked at time of first,inspection. <br /> 8. .All A.D.A. requirements shall be met. <br /> 9. No electric,plumbing, mechanical, or framing shall be covered without an inspection and <br /> approval first. <br /> 10. All Garages shall comply with.section R302.6 of the F.B.C..(Fire Separation). <br /> 11. Appliances-shall not be installed in a location where subject to mechanical damage finless <br /> protected by approved barriers. M303.4:of the F.B.0 <br /> 12. Water.heaters shall comply with section P607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M13.08.1 <br /> 14. Return air in all bedrooms. F.B.C. M1620.4 <br /> 15. Smoke detectors are to be'installed in accordance with R313.1 of the F.B.C. <br /> 16:.All glazing requirements are to be in accordance with R308.4,of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board"shall not be used as a backer.in showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all locations requiring an AFCI type breaker. <br /> 20. Carbon monoxide alarms:will be required m new construction that uses fossil=burning heating <br /> or appliances or an attached garage. They shall be,installed in accordance with the F.R.C. <br /> 21. All plumbing, mechanical, and electrical shall be separate from unit to.unit. This includes all . <br /> underground plumbing and electric. <br /> 22. All 2016 N.-E.C. Codes.will be enforced. <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11 of the 201-6 N.E.0 <br /> 24: hi accordance with the Land Development Code, lots shall be sodded before final of least 10 <br /> feet around the structure: <br /> 25.Blower door test shall be provided before.C.O.. <br /> 26 A copy of the enemy cacls shall be with permit at all times. <br /> 27. C60y of final insulation report shall be:provided with:-permit before:final <br /> 28.No fence,:pool or screen-enclosure -is.ksued with this permit <br /> RRE:-Finished Floor Elevation <br /> F.B.C-Florida Building Code 6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code (2016) <br />