Laserfiche WebLink
Single Family Dwelling <br /> Plan Review Comments <br /> 1: F.F.E. shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> I Lots shall be graded to comply with R401.3 of the F.B.C. <br /> 3. Compaction test required if.24" or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.O.W. use permit. All 4 sides of driveway thru the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met. <br /> 7. All property:markers shall be uncovered and marked at time of first inspection. <br /> 8. All A.D.A. requirements shall be met. <br /> 9. No electric, plumbing, mechanical, or framing shall be covered without an inspection and <br /> approval first. <br /> 10. All Garages shall comply with section R302..6 of the F.B.C..(Fire Separation). <br /> 11. Appliances shall not be installed in a location where subject to mechanical damage <br /> .unless <br /> protected by approved barriers. M303.4-of the F.B-.0 <br /> 12. Water,heaters shall comply with section.P607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished_ grade. M13:08.1 <br /> 14. Return air in all bedrooms. F.B.C. M1620.4 <br /> 15: Smoke detectors are to be installed in accordance with R313.1 of the F.B.C. <br /> 16. All glazing requirements are to be in accordance with R308:4 of the F.B.C: <br /> 17. All means of egress are to be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board" shall not be used as a backer in showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all.locations requiring an AFCI type breaker: <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil,burning heating <br /> or appliances or ari attached garage_: They shall be installed in accordance with the F.B.C. <br /> I. All plumbing, mechanical, and electrical shall be separate from unit to:unit. This includes all <br /> underground plumbing and electric. <br /> 22. All 2016 NX.C: Codes will be enforced. <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11 of the 2016 N:E:C <br /> 24. In accordancemith the Land Development Code, lots shall be sodded before final at least 10 <br /> feet around the structure: <br /> 25. Blower door test shall be provided before, <br /> 26. A copy of the energy eacls shall be with Permit at,all tines <br /> 27. Copy,of Fnal insulation report shall be.:provided with:permit before.fnaL <br /> 28:No fence..eool.or screen-enclosure is:issued with this pern:it.- <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C-Florida Building Code 6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />