Laserfiche WebLink
Single Family Dwelling <br /> Plan Review Comments <br /> 1. F.F.E. shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be.graded to comply with R401.3 of the F.B.C. <br /> 3. Compaction test required if.24"or.more of fill dirt-is brouglit in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.O.W. use permit. All 4 sides of driveway thru'the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met: <br /> 7. All property markers shall be uncovered and marked at time of first inspection. <br /> 8. All A.D.A.requirements shall be met. <br /> 9. No.electric,plumbing, mechanical, or framing shall be.covered without an.inspection and <br /> approval first. <br /> 10. All.Garages shall comply with section R302.6 of the F.B.C..(Fire Separation). <br /> I L Appliances shall not be installed in a location where subject to mechanical damage unless <br /> protected by approved barriers. M303 A.of the F.B.0 <br /> 12. Water heaters shall comply with section.P607.3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above_ finished grade, M13.08.1 <br /> 14. Return air in all bedrooms. F.B.C. MI6120.4 <br /> 15.-Smoke detectors are to be 'installed in accordance with R313.1 of theRB.C. <br /> 16. All glazing :requirements are to be in accordance with R308A of the F.B.C. <br /> 17. All means of egress are to.be in accordance with R311 of the F:B.C. <br /> 18: "Green gypsum board"shall not be used as a backer in.showers or tubs. R702.4:2:F.B.C. <br /> 19. Combination-t ype AFCI breakers are required at all locations requiring an AFCI type breaker: <br /> 20. Carbon monoxide alarms.will be required in new construction that uses fossil=burning heating <br /> or appliances or an attached garage: They shall be installed in accordance with-the F.B:C: <br /> 21. All plumbing,mechanical, and electrical shall be separate from unit to:unit: This includes all <br /> underground plumbing and electric. <br /> 22. All 20 :E 16 N .C. Codes will be enforced. <br /> 21 Tamper, Resistant Receptacles in accordance with 406.11 of the 2016 N.E:C <br /> 24: In accordance with.the Land Developmerit Code, lots shall be sodded'before final.at least 10 <br /> feet around the structure. <br /> 25.Blower door test and blown in insulation card shall be provided before C.O. <br /> 26.A copy of the energy eacls shall be with permit at all tunes <br /> 2Z Cotiy of final insulation repoil shall be.:provided W&permit before:fnaL <br /> 28: No fence;:pool or screen enclosure is:issued with this permit <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C- Florida Building Code 6t'Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />