Laserfiche WebLink
Single Family Dwelling <br /> Plan Review Comments <br /> 1: F.F.E. shall be a minimum of 8"above the road elevation and an engineered site plan. <br /> I Lots shall be graded to comply with R401.3 of the F.B.C. <br /> 3. Compaction test required if 24"or more of fill dirt-.is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5. Driveways require a R.O.W.use permit. All 4 sides of driveway thru the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met: <br /> 7. All property markers shall be uncovered and marked at time of first inspection. <br /> on. <br /> All A.D.A. requirements shall be met. <br /> 9. No electric,plumbing_, mechanical, or framing shall be covered without an.inspection and <br /> approval first. <br /> 10. All Garages shall comply with section R3,02._6 of the F.B.C.,(Fire Separation). <br /> I L Appliances shall not be installed in a location where subject to mechanical damage.unless <br /> protected by approved barriers. M303.4 of the F.B.0 <br /> 12. Water heaters shall comply with section P60.T3 of the F.B.C. <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished_ grade, M1308.1 <br /> 14. Return air in All'bedrooms. F.B.C. M1620.4 <br /> 15. Smoke detectors are to be 'installed in accordance with R313..1 of the F.B.C. <br /> 16. All glazing requirements afire to be in accordance with R308.4 of the F.B.C. <br /> 17. All means of egress are to be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board shall not be used as a backer in showers or tubs. R702.4.2 F.B.C. <br /> 19. Combination-type AFCI breakers are required at all locations requiring an AFCI type breaker: <br /> 20. Carbon monoxide alarms:will be required in new construction that uses fossil=burning heating <br /> or appliances or an attached garage: They shall be installed in accordance with the F.B:C: <br /> 21. All plumbing, mechanical, and.electrical shall be separate from unit to:unit. This includes all <br /> underground plumbing and electric: <br /> 22. Ali 2016 N.E.C. Codes will be enforced. <br /> - <br /> 23. Tamper- Resistant Receptacles in accordance with 406.11 of the 2016 NX.-C <br /> 24: In accordance with.the Land Development Code, lots shall be sodded before final at least 10 <br /> feet around the structure: <br /> 25. Blower door test and blown in insulation card shall be provided before C.O. <br /> 26. A copy of the enerzy eacls shall be with permit at all titnes. <br /> 27. Copy of Fnal insulation report shall be..nroWded with:perih t before-final <br /> 28.No fence:-pool or screen enclosure is issued with this permit <br /> F.F.E.-Finished Floor Elevation <br /> F.B.C- Florida Building Code 6th Edition <br /> R.O.W.-Right of Way <br /> A.D.A.-Americans with Disabilities Act N.E.C.-National Electric Code(2016) <br />