s.�Standby systemsLCLA
<br /> P,oworGonuration
<br /> Date: December 17,2018 BOM No.: 20226031
<br /> Reference: American House Zephyrhills SG400 :EU D;:(tSquareeD Breakers
<br /> We are pleased to offer the following quote for the above project:
<br /> Quantity 1 -G.enerac Industrial gaseous engine-driven generator,turbocharged/aftercooled 12 cylinder 21.9L.
<br /> engine, consisting of the following features and accessories:
<br /> .`0 kW g wiredfo'r 40 Rahn
<br /> Stationary Emergency-Standby rated
<br /> a '�120/2'08:,17/-1C'three°�hase"�`6. O�Hz1 . -
<br /> Level'2.Acoustic.Enclosure,'Alu inuree.
<br /> lndustrial=Gre Bakedz®,ntPowder;G`aatFiiii's
<br /> ' UL220<
<br /> EPA Gertifie"
<br /> Power-Zone Digital Control Panel for Single or MPS Generators
<br /> o Meets NFPA 99 and 110 requirements
<br /> o Temp Range-40 to 70 degrees C
<br /> o Humidity 2—95% (Non Condensing)
<br /> o UI_6200 ,:
<br /> o C-ETL-US
<br /> o CE
<br /> oFCC
<br /> o : IEC801 (Radiated Emissions, Susceptibility, and.Surge Immunity)
<br /> o " 7"Resistive Color Touchscreen
<br /> Built-in Wi-Fi;.Bluetooth, and:Webserver
<br /> IP65 (front)
<br /> ■ Auto/Manual/Off key switch,Alarm Indication, Not in Auto Indication, audible alarm,
<br /> emergency stop switch
<br /> o Dual Core Digital Microprocessor
<br /> ■ RS485, Ethernet and CANbus ports
<br /> o All engine sensors are 4-20ma for minimal:interference
<br /> • Sensors: Oil Pressure, optional Oil Temp,Coolant Temp and Level; Fuel Level/Pressure.:
<br /> (Where:applicable), Engine Speed, DC Battery Voltage, Run-time Hours, Generator.
<br /> Voltages,Amps,,Frequency, Power, Power Factor.:
<br /> Alarm Status: Low or High AC Voltage, Low or High Battery Voltage; Low or High
<br /> Frequency,.Pre-low or Low Oil Pressure,"Pre.-high or High Oil Temp.(optional) Low Water
<br /> Level and Temp, Pre-high or High Engine Temp, High, Low, and Critical-low Fuel
<br /> Level/Pressure(where applicable),:Overcrank, Over and Under Speed, Unit Not in
<br /> Automatic "
<br /> Programmable 1/0:,
<br /> ■ Built-in PLC for special applications
<br /> o Engine function monitoring and control:
<br /> Full range standby operation; programmable auto crank, Emergency Stop,Auto-Off
<br /> Manual switch
<br /> ■ Isochronous Governor
<br /> •_ 0.25% digital frequency regulation with: soft-start ramping-adjustable, gain
<br /> adjustable, overshoot limit-adjustable
<br /> ■ 3 Phase RMS Voltage.Sensing
<br /> • +/-0.5% digital voltage regulation'with: soft-start Voltage ramping-adjustable;.loss:
<br /> of sensing protection:'-adjustable, negative'power limit-adjustable, HYLo voltage .
<br /> limit-:adjustable,V/F slope and gain-adjustable,fault protection
<br /> o Service reminders,trending,fault history(alarm log)
<br /> o. 12T function for full generator protection
<br /> -Page 1 of ..
<br />
|