<br /> TABLE 2A: STEEL or STRUCTURAL CONCRETE DECKS-NEW CONSTRUCTION,REROOF(Tear-Off)or RECOVER
<br /> SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION,BONDED TOP INSULATION,BONDED ROOF COVER
<br /> System Deck Base Insulation Layer I Top Insulation Layer I 7MDP
<br /> No. Roof Cover(Note 16)
<br /> (Note 1) Type Fastener Attach Type Attach (psf)MULE-HIDE TPO-c APPLICATIONS:
<br /> Min.22 ga.,type B,Grade 33 Min.1.5-inch Poly ISO 1,H- Min.1.0-inch base insulation and/or Mule Hide
<br /> SC-1 steel or min.2,500 psi Note 2 1 per 3.2 ftZ Min.0.25-inch Dens Deck Prime or HELIX 20 B/TPO-c BA or
<br /> 1
<br /> Shield Poliso HP-H -45.0*
<br /> structural concrete , y SECUROCK Gypsum-Fiber Roof Board Aqua Base 120 BA
<br /> Min.22 ga.,type B,Grade 33 Min.2-inch Poly ISO 1,H- Min.1.0-inch base insulation and/or Mule-Hide TPO-c/TPO-c BA or
<br /> SC-2 steel or min.2,500 psi Shield,Polyiso HP-H Note 2 1 per 4.0 ftZ Min.0.25-inch Dens Deck Prime or HELIX Aqua Base 120 BA -45.0*
<br /> structural concrete SECUROCK Gypsum-Fiber Roof Board
<br /> Min.22 ga.,type B.Grade 33 Min.0.5-inch Dens Deck or Min.1.5-inch ACFoam II,Poly ISO 2, Mule-Hide TPO-c/TPO-c BA or
<br /> SC-3 steel or min.2,500 psi Dens Deck Prime Note 2 1 per 2.0 ftZ ENRGY 3,Poly ISO 1 or H-Shield followed OB500 Aqua Base 120 BA -37.5*
<br /> structural concrete by Min.0.25-inch Dens Deck Prime
<br /> Min.22 ga.,type B,Grade 33
<br /> SC-4 steel or min.2,500 psi Min.2-inch Poly ISO 1.H- Note 2 1 per 4.0 ftZ Min 0.25-inch SECUROCK Gypsum-Fiber OB500 Mule-Hide TPO-c/TPO-c BA or -37.5*
<br /> structural concrete Shield,H Shield CG Roof Board Aqua Base 120 BA
<br /> Min.22 ga.,type B,Grade 33 Min.1.5-inch ACFoam II,Poly Mule-Hide TPO-c/TPO-c BA or
<br /> SC-5 steel or min.2,500 psi ISO 1,Poly ISO 2,H-Shield CG, Note 2 1 per 2.0 ftZ Additional layers of base insulation OB500 pule Base 120-c -45.0*
<br /> structural concrete ENRGY 3
<br /> Min.22 ga.,type B,Grade 33 Min.1.5-inch ACFoam II,Poly Min.0.25-inch Dens Deck,Dens Deck Mule-Hide TPO-c/TPO-c BA or
<br /> SC-6 steel or min.2,500 psi ISO 1,Poly ISO 2,H-Shield CG, Note 2 1 per 2.0 ftZ prime OB500 Aqua Base 120 BA -45.0*
<br /> structural concrete ENRGY 3
<br /> Min.22 ga.,type B.Grade 33 Min.0.5-inch Dens Deck or Z Min.1.5-inch ACFoam II,Poly ISO 2, Mule-Hide TPO-c/TPO-c BA or
<br /> SC-7 steel or min.2,500 psi Dens Deck Prime Note 2 1 per 2.0 ft ENRGY 3,H-Shield or Poly ISO 1 OB500 Aqua Base 120 BA -45.0*
<br /> structural concrete
<br /> Min.22 ga.,type B,Grade 33 Min.2.0-inch ACFoam II,Poly Mule-Hide TPO-c/TPO-c BA or
<br /> SC-8 steel or min.2,500 psi ISO 1,Poly ISO 2,H-Shield CG, Note 2 1 per 4.0 ftZ Additional layers of base insulation OB500 Aqua Base 120 BA -45.0*
<br /> structural concrete ENRGY 3
<br /> Min.22 ga.,type B,Grade 33 Min.2.0-inch ACFoam II,Poly
<br /> SC-9 steel or min.2,500 psi ISO 1,Poly ISO 2,H-Shield CG, Note 2 1 per 4.0 ftZ Min.0.25 inch Dens Deck,Dens Deck OB500 Mule-Hide 1 /TPO-c BA or
<br /> 120 B
<br /> Prime -45.0*
<br /> structural concrete ENRGY 3 Aqua Base 20 BA
<br /> Min.22 ga.,type B,Grade 33 Min.1.5-inch Poly ISO 1,H- Z Min.0.25-inch SECUROCK Gypsum-Fiber Mule-Hide TPO-c/TPO-c BA or
<br /> SC-10 steel or min.2,500 psi Shield,H-Shield CG Note 2 1 per 3.2 ft Roof Board OB500 Aqua Base 120 BA -45.0*
<br /> structural concrete
<br /> Min.22 ga.,type B,Grade 33 Min.2-inch Poly ISO 1,H- Z Min 0.25-inch SECUROCK Gypsum-Fiber Mule-Hide TPO-c/TPO-c BA or
<br /> SC-11 steel or min.2,500 psi Shield,H-Shield CG Note 2 1 per 2.67 ft Roof Board OB500 Aqua Base 120 BA -45.0*
<br /> structural concrete
<br /> Min.22 ga.,type B,Grade 33 Min.2-inch Poly ISO 1,H- Z Min 0.25-inch SECUROCK Gypsum-Fiber Mule-Hide TPO-c/TPO-c BA or
<br /> SC-12 steel or min.2,500 psi Shield,H-Shield CG Note 2 1 per 1.6 ft Roof Board OB500 Aqua Base 120 BA -60.0
<br /> structural concrete
<br /> MULE-HIDETPO-CFLEECE'BACK APPLICATIONS:
<br /> Exterior Research and Design,I.I.C.d/b/a Trinity ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
<br /> Certificate of Authorization#9503 CH EDITION(2017)FBC NON-HVHZ EVALUATION Revision 5:09/11/2017
<br /> Prepared by: Robert Nieminen,PE-59166 Mule-Hide TPO-c Single Ply Roof Systems;(608)365-3111 Appendix 1,Page 6 of 27