Laserfiche WebLink
following: Henry Valve Co., Parker Hannifin Corp. Refrigeration & Air Conditioning <br /> Div., Sporlan Valve Co. <br /> 2. Solenoid Valves: <br /> a. Two-way Solenoid Valves: Forged brass, designed to conform to ARI 760, <br /> normally closed, Teflon valve seat, NEMA 1 solenoid enclosure, 24 volt, 60 hertz, <br /> UL listed, 1/2" conduit adapter, 250' F temperature rating, 400 PSI working <br /> pressure. <br /> Manual Operator: Provide manual operator to open valve. <br /> b. Available Manufacturers: Subject to compliance with requirements, manufacturers <br /> offering solenoid valves which may be incorporated in the work include the <br /> following: Alco Controls Div., Emerson Electric Co.,Automatic Switch Co., Sporlan <br /> Valve Co. <br /> 2.5 REFRIGERATION ACCESSORIES <br /> A. Refrigerant Strainers: Brass shell end and connections, brazed joints, Monel screen, 100 mesh, <br /> UL-listed, 350 PSI working pressure. <br /> B. Moisture-Liquid Indicators: Forged brass, single port, removable cap, polished optical glass, <br /> solder connections, UL-listed 200' F (93' C)temperature rating, 500 PSI working pressure. <br /> C. Refrigerant Filter-Driers: Corrosion-resistant steel shell, steel flange ring and spring, wrought <br /> copper fittings, ductile iron cover plate with steel cap screws, replaceable filter-drier core, 500 <br /> PSI working pressure. All filter-driers shall meet the requirements of ARI Standard 710. Filter- <br /> Driers for heat pump systems shall be bi-flow type. <br /> D. Evaporator Pressure Regulators: Provide corrosion-resistant, spring-loaded, stainless steel <br /> springs, pressure operated, evaporator pressure regulator, in size and working pressure <br /> indicated,with copper connections. <br /> E. Refrigerant Discharge Line Mufflers: Provide discharge line mufflers as recommended by <br /> equipment manufacturer for use in service indicated, UL-listed. <br /> F. Available Manufacturers: Subject to compliance with requirements, manufacturers offering <br /> refrigeration accessories which may be incorporated in the work include the following: Alco <br /> Controls Div., Henry Valve Co., Parker-Hannifin Corp., Sporlan Valve Co. <br /> PART 3- EXECUTION <br /> 3.1 REFRIGERANT PIPING INSTALLATION <br /> A. Refrigerant piping shall be sized as per recommendations of the air conditioning equipment <br /> manufacturer. Provide, upon request, copies of manufacturer's calculations, specifically when <br /> distance between system components exceeds standard published data. <br /> B. Piping shall be filled with dry nitrogen while soldering. <br /> C. Provide all necessary valves, traps, filter/dryers, sight glass, etc. as required for a complete and <br /> ready to operate installation. Include accessible service fittings. <br /> D. Provide long sweep elbows or junction boxes at the ends of conduit to facilitate pulling of <br /> refrigerant pipes. <br /> CEA#18010 REFRIGERANT PIPING SYSTEMS 23 23 00-3 <br /> COPYRIGHT©2016 CONSULTING ENGINEERING ASSOCIATES, INC. <br />