Laserfiche WebLink
System Information For <br /> JLS Automotive <br /> • This is an AMEREX IS System: <br /> • Piping to be 3/ & 1" galvanized <br /> • Pull station is to be mounted at 48". <br /> Detection to be fusible links of 280* <br /> • Upon system actuation exhaust will shut down <br /> System to be tied into bell <br /> All penetrations shall be sealed. <br /> • Installation will comply with FFPC 6th ed., NFPA 17 <br /> 2013 ed., Manufacturers Specifications, and all local <br /> codes and standards <br />