Laserfiche WebLink
MIKEN FIRE PROTECTION, INC. <br /> 1019 WILDROSE DRIVE ' <br /> LUTZ, FL. 33549 <br /> HYDRAULIC CALCULATIONS <br /> FOR <br /> PROFESSIONAL HAIR - OFFICE TRUSS AREA <br /> CORREIA DRIVE - ZEPHYRHILLS, FL. <br /> FILE NUMBER: PROFESSIONAL HAIR OFFICE TRUSS . SDF <br /> DATE: 8/19/19 <br /> Curtis Engineering Service, LLC <br /> -DESIGN DATA- CA#31561 <br /> James M. Curtis, P.E. <br /> OCCUPANCY CLASSIFICATION: LIGHT HAZARD PE#37912 <br /> 29775 Bayhead Road <br /> DENSITY: . 10 gpm/sq. ft. Dade City, FL 33523 <br /> AREA OF APPLICATION: 1000 sq. ft. PER CONCEALED SPACE SPRINKLER <br /> MANUFACTURER REQUIREMENT <br /> COVERAGE PER SPRINKLER: VARIES - 134 sq. ft. <br /> NUMBER OF SPRINKLERS CALCULATED: 10 sprinklers \\o\� �IGEN5��//���� <br /> TOTAL SPRINKLER WATER FLOW REQUIRED: 161. 6 gpm <br /> No.3 912 0 .- <br /> TOTAL WATER REQUIRED (including hose) : 261 . 6 gpm <br /> 0 <br /> ® T F <br /> FLOW AND PRESSURE (@ BOR) : 161. 6 gpm @ 52 .2 psioo <br /> SPRINKLER ORIFICE SIZE: 1/2 inch ®® �'�®N�X,��\\\\ <br /> NAME OF CONTRACTOR: MIKEN FIRE PROTECTION, INC. <br /> DESIGN/LAYOUT BY: JAMES M. DUPREE <br /> AUTHORITY HAVING JURISDICTION: CITY OF ZEPHYRHILLS BUILDING AND FIRE <br /> CONTRACTOR CERTIFICATION NUMBER: 22111800012011 <br /> CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 1608008510 ) <br /> HRS SYSTEMS, INC. <br />