Laserfiche WebLink
MIKEN FIRE PROTECTION, INC. <br /> 1019 WILDROSE DRIVE ' <br /> LUTZ, FL. 33549 <br /> HYDRAULIC CALCULATIONS <br /> FOR <br /> PROFESSIONAL HAIR - WAREHOUSE AREA <br /> CORREIA DRIVE - ZEPHYRHILLS, FL. <br /> FILE NUMBER: PROFESSIONAL HAIR WH. SDF <br /> DATE: 8/19/19 <br /> -DESIGN DATA- Curtis Engineering Service, LLC <br /> CA# 31561 <br /> OCCUPANCY CLASSIFICATION: ORDINARY HAZARD GROUP 2 James M. Curtis, P.E. <br /> PE#37912 <br /> DENSITY: .20 gpm/sq. ft. 29775 Bayhead Road <br /> Dade City, FL 33523 <br /> AREA OF APPLICATION: 1500 sq. ft. <br /> COVERAGE PER SPRINKLER: VARIES - 126 Max sq. ft. <br /> NUMBER OF SPRINKLERS CALCULATED: 13 sprinklers \\\ �S• :_cC1/��/// <br /> XP <br /> TOTAL SPRINKLER WATER FLOW REQUIRED: 344 . 7 gpm �a <br /> N .3912 ° <br /> TOTAL WATER REQUIRED (including hose) : 594 . 7 gpm _ <br /> ° A F <br /> FLOW AND PRESSURE (@ BOR) : 344 . 7 gpm @ 53 . 1 psi <br /> SPRINKLER ORIFICE SIZE : 1/2 inch ✓,j10. ®NAL <br /> ///IIIIII\e\\\\ <br /> NAME OF CONTRACTOR: MIKEN FIRE PROTECTION, INC. <br /> DESIGN/LAYOUT BY: JAMES M. DUPREE <br /> AUTHORITY HAVING JURISDICTION: CITY OF ZEPHYRHILLS BUILDING AND FIRE <br /> CONTRACTOR CERTIFICATION NUMBER: 22111800012011 <br /> CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 1608008510 ) <br /> HRS SYSTEMS, INC. <br />