Air System Design Load Summary for AHU-1/2 <br /> Project Name:LS Zeypherhills 08/09/2019 <br /> Prepared by:Gregory L.Cherok 09:12PM <br /> DESIGN COOLING DESIGN HEATING <br /> COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG <br /> COOLING OA DB/WB 91.6°F/76.9°F HEATING OA DB/WB 36.0°F/30.3°F <br /> Sensible Latent Sensible Latent <br /> ZONE LOADS - Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) <br /> Window&Skylight Solar Loads 72 ft2 1925 72 ft2 - <br /> Wall Transmission 1583 ft2 2775 1583 ft2 3436 <br /> Roof Transmission 3000 ft2 6482 3000 ft2 4746 <br /> Window Transmission 72 ft2 715 - 72 ft2 1714 <br /> Skylight Transmission 0 ft2 0 - 0 ft2 0 <br /> Door Loads 0 ft2 0 - 0 ft2 0 <br /> Floor Transmission 3000 ft2 0 - 3000 ft2 3964 <br /> Partitions 755 ft2 366 - 755 ft2 0 <br /> Ceiling 0 ft2 0 - 0 ft2 0 - <br /> Overhead Lighting 6000 W 20472 - 0 0 - <br /> Task Lighting 0 W 0 - 0 0 <br /> Electric Equipment 1628 W 5553 - 0 0 - <br /> People 41 9862 7163 0 0 0 <br /> Infiltration - 0 0 - 0 0 <br /> Miscellaneous 0 0 - 0 0 <br /> Safety Factor 10%/10% 4815 716 10% 1386 0 <br /> >>Total Zone Loads 52965 7879 15245 0 <br /> Zone Conditioning - 53589 7879 - 14637 0 <br /> Plenum Wall Load 0% 0 - 0 0 - <br /> Plenum Roof Load 0% 0 0 0 - <br /> Plenum Lighting Load 0% 0 0 0 - <br /> Retum Fan Load 3033 CFM 0 - 3033 CFM 0 - <br /> Ventilation Load 600 CFM 10019 16254 600 CFM 21802 0 <br /> Supply Fan Load 3033 CFM 0 - 3033 CFM 0 - <br /> Space Fan Coil Fans - 0 - - 0 <br /> Duct Heat Gain/Loss 0% 0 - 0% 0 - <br /> >>Total System Loads 63608 24132 36439 0 <br /> Central Cooling Coil - 63608 24141 - 0 0 <br /> Central Heating Coil -1 0 - 36439 - <br /> >>Total Conditioning 636081 24141 364391 0 <br /> Key: Positive values are clg loads Positive values are htg loads <br /> Negative values are htg loads I Negative values are cig loads <br /> Hourly Analysis Program 5.11 Page 3 of 7 <br />