r <br /> Wiring & Configuration <br /> Device loop Auxiliary&smoke power outputs(TB3) <br /> The system provides one device loop circuit with a total capacity The control panel provides two auxiliary power T133 <br /> of 125 detectors and 125 module addresses.The loop circuit is outputs that can be used for powering ancillary <br /> supervised for opens,shorts,and grounds. equipment such as remote annunciators and two No <br /> (1) <br /> wire smoke detectors, Aux 2 can be software NC <br /> specifications <br /> Circuit VS4 VS1 selected tooperate continuously.The circuit is <br /> ' <br /> Device loops One Class B or A One e Class B or A loop, supervised for shorts and grounds. <br /> loop,supporting 125 ( supporting64 devices of - - (2) NO <br /> Circuit specifications <br /> detectors and 125 j any kind. Circuit voltage 21.9 to 28.3 V <br /> modules.Expandable to 1 range _ _ _ @ NC <br /> four loops. I Resettable circuit 24 VDC nominal at 500 mA (3) <br /> Communication Maximum 20 V peak-to-peak _ (Aux power 2) NO <br /> line voltage Continuous circuit 24 VDC nominal at 500 mA. <br /> Circuit current 0.5 A max (Aux power 1) Use this circuit for powering O <br /> Circuit 660 total,0.5 pF,max two-wire smoke detectors. <br /> impedance (4) <br /> Isolators 64 maximum Note:Any current above 0.5 amp connected to both Aux <br /> 1 and 2 will reduce the total available NAC power by that O <br /> Signal Supported on a system-wide basis(all device loops) amount. <br /> Synchronization when using an addressable notification appliance (1)Trouble <br /> circuit(NAC)module and Genesis or Enhanced <br /> Integrity notification appliances. (2)Supervisory <br /> Alarm,trouble,and supervisory relay(TB3) (3)Alarm <br /> Class Wr,.g ClassAwiring The trouble relay is normally-open, held closed, <br /> and opens on any trouble event or when the (4)Smoke/Aux <br /> SLC A Data Line SLC A panel is de-energized.The supervisory relay is <br /> normally-open,and closes on any supervisory <br /> SLC B , i SLC B ,m �MPdL.I.P. <br /> event.The alarm relay changes over on any <br /> Loop Loop Loop card dW- device Loop card oa�L,na alarm event. <br /> Relay specifications <br /> Alarm Trouble Supervisory_ <br /> ----- ----- ------— - <br /> Notification appliance circuits(TB2) Type Form C Form A <br /> VS4 control panels come equipped with four notification appliance Voltage 24 VDC at 1 A resistive 24 VDC at 1 A resistive <br /> circuits.VS1 control panels come with two NACs. Each circuit can Relay circuits can only be connected to power-limited sources. <br /> be individually configured for continuous,temporal,synchronized, <br /> and coded output. <br /> Specifications VS4 VSi Annunciator loop(TB4) <br /> Circuit Type 4 Class B or 2 Class A I 2 Class B or 2 Class A The control panel provides a connection for up to eight serially <br /> with SA-CLA module driven and supervised remote annunciators. <br /> Voltage 24 VFWR <br /> Current 6.0 A total,2.5 A max. 1 3.75 A total,2.5 A max. Circuit specifications <br /> per circuit at 120/230 per circuit at 120/230 Device loops_ Class B(Style 10 or Class A(Style Z) <br /> VAC 60 Hz. VAC 60 Hz. Circuit voltage 2.55 V <br /> 5.0 A total,2.5 A max. 3.0 A total,2.5 A max. Circuit current 30 mA max <br /> per circuit at 230 VAC per circuit at 230 VAC Circuit Up to 8 annunciators or 4000 feet <br /> _ 50 Hz. i 50 Hz. impedance <br /> Impedance 26 0 total,0.35 pF max - — <br /> EOLR 15 K 0,�/2 W <br /> Class B Class A <br /> Synchronization Supported system-wide <br /> Channel) Channel Channel Channel <br /> Closs B wiring Class A wiring TB4 T64 <br /> NAC,- + + NAC,- + + <br /> 0 NAC1� jo , <br /> Annunciator Annunciator <br /> NAC2- + + EOLR + + CH1(+)IN CH1(+)IN <br /> NAC2+ - - CH1(-)IN CH1(-)IN <br /> TB2 T02 <br /> NAC3- + B2 - t9 CH2(+)IN CH2(+)IN <br /> e NAp. - - EOLR e + (9 CH2(-)IN CH2(-)IN <br /> e NAC4- + + - <br /> TBO TB6 <br /> Marking indicates output signal polarity when the circuit is active.Polarity reverses <br /> when the circuit is not active.Wire notification appliances accordingly.Notification <br /> appliance polarity shown in active state. <br /> 0 <br /> N <br /> Page 4 of 8 (> 17 t-. l V85005-0135 <br /> riot to t;,, usc„ -:u in:.talte,(ior: . issue1.3 V <br />