Laserfiche WebLink
Application Annunciator Wiring <br /> R-Series annunciators communicate with the FACP on the RS-485 Annunciator, Class A <br /> data riser.This can be configured for Class A or Class B commu- <br /> nication.Annunciators do not provide ground fault isolation. FACP Annunciator Annunciator <br /> RS485 CHI IN CHI IN <br /> These annunciators are stand-alone units that can be powered by CHI+ <br /> ' CH1(-)IN CH,(-)IN <br /> the FACP or by an approved power supply. CH - DH,(+)GDT 0 CHI(+)OUT <br /> CH2+ 0 CH1(-)OUT <br /> CH2- CH2(+)IN CH2(+j IN <br /> CH2(-)IN CH2(-)IN <br /> _ °a °o LISTED 24 VDC CH2(+)OUT 0 CH2(+j OUT <br /> ° � 00 0 SUPPLY CH2 I-)OUT 0CH2 OUT <br /> d � d 24 VDC+ 24V(+)IN 24V(+)IN <br /> e0 a� a 24 VDC- 24V(-)IN 24V(-)IN <br /> 00 <br /> n w o O a w 24V(+)OUT 0 24V(+)OUT <br /> 24V(-)OUT 0 24V(-)OUT <br /> � E GROUND GROUND <br /> RLCD-C RLED-C <br /> Annunciator, Class B <br /> 0._ ° <br /> ° FACP Annunciator Annunciator <br /> d°""10ve °00 o RS485 CHI(+)IN CHI <br /> ®®® °off°o IN <br /> °00°o CH7+ CH7(-)IN CHI(-j IN <br /> 000°o CH,_ CHI(+)OUT 0 CHI(+)OUT <br /> °oO°o CHI(-)OUT 0 CHI(-)OUT <br /> D 0 CH2(♦)IN 0 CH2(+)IN <br /> 0 CH2(-)IN 0 CH2(-)IN <br /> RLCD RLED24 <br /> LISTED 24 VDC 0 CH2(+)OUT 0 CH2(+)OUT <br /> Features by model RLCD RLCD-C RLED-C RLED24 SUPPLY 0 CH2(-)OUT 0 CH2(-)OUT <br /> Reset ✓ ✓ ✓ 24 VDC+ z4v(+)IN 24V(+)IN <br /> _. 24 VOC- 24V(-j IN 24V(-)IN <br /> Ack/Silence ✓ ✓ ✓ — 24V(+)OUT 0 24V(+j OUT <br /> Fire Alarm ✓ ✓ ✓ 24V(-)OUT 0 24v(-)our <br /> Supervisory ✓ ✓ ✓ <br /> GROUND GROUND <br /> Ground Fault ✓ ✓ ✓ —_ <br /> Trouble ✓ ✓ ✓ <br /> Controls Enabled ✓ ✓ ✓ <br /> Ack/Silence ✓ ✓ ✓ -- Expander <br /> Reset ✓ ✓ - - -Ex Ann unclator First Expander Secontl Expantler <br /> Signal Silence ✓ ✓ <br /> Drill ✓ ✓ OUT IN OUT IN OUT <br /> Lamp Test ✓ ✓ ✓ v(+) v(+) v(+)0 - -------j Ov(+) v(+)0 <br /> LCD Display ✓ ✓ F F F 0- - -------:- O F Fe <br /> Zone Active LEDs 16. 24" E E E 0- - -------;- E E 0 <br /> Zone Trouble LEDs - - 16 24 D D DO- - -------;- 0 D Do <br /> ------ --- -- c c c 0- --------- 0 c CO <br /> .zones 13-16 maybe selected as Supervisory on FX-64 and VS7 <br /> ., B B B 0- --------- B SO , <br /> zones 13-16 and 29-32 may be selected as Supervisory on FX-1000 and VS4 ; <br /> .._ A A A A 0 , <br /> ---------------------- <br /> Graphic Annunciator Interface <br /> The GCI Graphic Annunciator Driver is an interface card that <br /> connects the fire alarm control panel to the display panel of an Remote Keyswitch <br /> LED-based graphic annunciator. Annunciator LSRA-RK <br /> The annunciator card supports 32 LEDs and 16 switches on the KEYSWITCH(-j <br /> graphic panel display. It includes status LEDs and an internal KEYSWITCH <br /> buzzer. <br /> The graphic interface is supplied with snap track mounting. It is Keyswitch Specifications <br /> attached to a plastic mounting rail that requires two EIA panels. Maximum 5 Vdc <br /> voltage <br /> The annunciator communicates with the FACP on the RS-485 -Maximum 200 mA <br /> data riser.This can be configured for Class A or Class B commu- current <br /> nication.The annunciator does not provide ground fault isolation. Mounting 2-1/2 in(64 mm) <br /> It is a stand-alone unit that can be powered by the FACP or by an deep 1-gang box <br /> approved power supply. Termination _Screw terminals <br /> Maximum 12 AWG <br /> Graphic Annunciator Interface Specifications - wire size (2.5 mm sq) <br /> Alarm current _ _ 146 n-A at 24 Vdc(with 36 LEDs ON) Contact Normally open <br /> Standby current 36 mA at 24 Vdc(with no LEDs ON) configuration <br /> Maximum current 10 mA per LED <br /> Page 2 of 4 U A 7 A 5 F I E EK35005-0128 <br /> TSrt to i)c ua[^ci ICr issue 1 <br />