My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
20-22256
Zephyrhills
>
Building Department
>
Permits
>
2020
>
20-22256
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/25/2021 10:50:22 AM
Creation date
3/25/2021 10:50:19 AM
Metadata
Fields
Template:
Building Department
Company Name
ZEPHYR LAKES
Building Department - Doc Type
Permit
Permit #
20-22256
Building Department - Name
DR HORTON INC
Address
8029 SAIL CLOVER LN
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
33
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
MANDATORY REQUIREMENTS - (Continued) <br /> ❑R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through where open combustion air ducts provide combustion air to <br /> open combustion fuel burning appliances,the appliances and combustion air opening all <br /> be located outside the building thermal envelope or <br /> enclosed in a room,isolated from inside the thermal envelope.Such rooms shall be s led and insulated in accordance with the envelope requirements <br /> of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the ba ement wall R-value requirement.The door into the room shall be <br /> fully gasketed and any water Iines.and ducts in the room insulated in accordance with ection R403.The combustion air duct shall be insulated where it <br /> passes through conditioned space to a minimum of R-8. <br /> Exceptions: <br /> 1. Direct vent appliances with both intake and exhaust pipes installe continuous to the outside. <br /> 2. Fireplaces and stoves complying with Section R402.4.2 and Secti n R1006 of the Florida Building Code,Residential. <br /> ❑R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal nvelope shall be sealed to limit air leakage <br /> between conditioned and.unconditioned spaces.All recessed luminaires shall be IC-rat d and labeled as having an air leakage rate not <br /> more than 2.0 cfm(0.944 Us)when tested in accordance with.ASTM E283 at a 1.57 ps (75 Pa)pressure differential.All recessed <br /> luminaires shall be sealed with a gasket or caulk between the housing and the interior all or ceiling covering. <br /> SECTION R403 SYS EMS <br /> R403.1 Controls. <br /> ❑ R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. <br /> ❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having s pplementary electric-resistance heat shall have controls <br /> that,except during defrost,prevent supplemental heat operation when the heat ump compressor can meet the heating load. <br /> ❑ R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways <br /> for air distribution systems shall be considered ducts or plenum chambers,sh II be constructed and sealed in accordance with Section <br /> C403.2.9.2 of the Commercial Provisions of this code and shall be shown to m et duct tightness criteria below. <br /> Duct tightness shall be verified by testing in accordance with ANSI/RESNET/I C 380 by either individuals as defined in Section 553.993(5)or <br /> (7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f,(g)or(i),Florida Statutes,to be"substantially leak free"in <br /> accordance with Section R403.3.3. <br /> ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturer's designation for an air leakage of no more than 2 percent <br /> of the design airflow rate when tested in accordance with ASHRAE 193. <br /> ❑ R403.3.3 Duct testing(Mandatory). Ducts shall be pressure tested to determ no air leakage by one of the following methods: <br /> 1, Rough-in test:Total leakage shall be measured with a pressure ifferential of 0.1 inch w.g. (25 Pa)across the system,including the <br /> manufacturer's air handler enclosure if installed at the time of th test.All registers shall be taped or otherwise sealed during the test. <br /> 2. Postconstruction test:Total leakage shall be measured with a pr ssure differential of 0.1 inch w.g. (25 Pa)across the <br /> entire system,including the manufacturer's air handler enclosure Registers shall be taped or otherwise sealed during the <br /> test. <br /> Exceptions: <br /> 1. A duct air leakage test shall not be required where the ducts nd air handlers are located entirely within the building <br /> thermal envelope. <br /> 2. Duct testing is not mandatory for buildings complying by Sect on 405 of this code. <br /> A written report of the results of the test shall be signed by the part conducting the test and provided to the code official. <br /> ❑R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. <br /> ❑R403.4.Mechanical system piping insulation(Mandatory). Mechanical system pipi g capable of carrying fluids above 105°F(41°C) <br /> or below 55°F(13°C)shall be insulated to a minimum of R-3. <br /> ❑ R403.4.1 Protection of piping insulation. Piping insulation exposed to we ther shall be protected from damage,including that <br /> caused by sunlight,moisture,equipment maintenance and wind,and shall provi a shielding from solar radiation that can cause <br /> degradation of the material..Adhesive tape shall not be permitted. <br /> ❑ R403.5.1 Heated water circulation and temperature maintenance.systems( andatory). Heated water circulation systems shall be in <br /> accordance with Section R403.5.1.1.Heat trace temperature maintenance syst ms shall be in accordance with Section R403.5.1.2. <br /> Automatic controls,temperature sensors and pumps shall be accessible. Manu I controls shall be readily accessible. <br /> R403.5.1.1 Circulation.systems. Heated water circulation systems hall be provided with a circulation pump.The system return <br /> ❑ pipe shall be a dedicated return pipe or a cold water supply pipe.Grav ty and thermosiphon circulation systems shall be prohibited. <br /> Controls for circulating hot water system pumps shall start the pump b sed on the identification of a demand for hot water within the <br /> occupancy.The controls shall automatically turn off the pump when th water in the circulation loop is at the desired temperature and <br /> when there is no demand for hot water. <br /> ❑ R403.5.1.2 Heat trace systems. Electric heat trace systems shall co ply with IEEE 515.1 or UL 515.Controls for such systems <br /> shall automatically adjust the energy input to the heat tracing to mainti in the desired water temperature in the piping in accordance <br /> with the times when heated water is used in the occupancy. <br /> 1 1/5/201 9 1 1:45 AM EnergyGauge@ USA 6.0.02(Rev. 1)-FlaRes2017 FBC 6th Ed tion(2017) Compliant Software Page 2 of 5 <br />
The URL can be used to link to this page
Your browser does not support the video tag.