S <br /> C'y <br /> N <br /> HYDRAULIC CALCULATIONS E <br /> 53600 'at <br /> FOR <br /> FRATERNAL ORDER OF EAGLES <br /> TAT OF ztt <br /> ZEPHYRHILLS, FL. 1.0 <br /> A% <br /> 0 N <br /> JAN 13, 2e20 <br /> -DESIGN DATA- 01/16/2020 <br /> .00CUPANCY CLASSIFICATION: LIGHT HAZARD <br /> SYSTEM TYPE: WET SYSTEM <br /> DISCHARGE: .1 .gpm/s.f. <br /> AREA OF APPLICATION: 1500, sq. ft: <br /> COVERAGE PER SPRINKLER: 196 sq. ft. <br /> TOTAL SPRINKLER WATER FLOW REQUIRED: 259.8 gpm <br /> TOTAL WATER REQUIRED (including hose): 359.8 gpm <br /> FLOW & PRESSURE (at base of riser): 259.8 gpm @ 44.2 psi <br /> FLOW & PRESSURE (at source). 359.8 gpm @ 51.1 psi <br /> SAFETY FACTOR: 6.6 Psi <br /> SPRINKLER ORIFICE SIZE: 1/2" 5.6 K <br /> AUTHORITY HAVING 3URISDICTION: FIRE MARSHAL <br /> DRAWN BY: R THOMPSON NICET 111 #131349 <br /> FLORIDA FIRE SERVICE INC- RIVERVIEW FL.. <br /> JJ CONSULTING GROUP, INC. <br /> CA LICENSE#31838 <br /> JORGE J. SALGADO, P.E.#5381313 <br /> 20D I Tmew—L.CIRCLE <br /> #1509 <br /> ORLANDO,FL 32837 <br />