• ACS annunciators per - City and County of Denver.
<br /> NCA-2..............I......................32 addresses x 64 or 96 points . CCCF listed.
<br /> NOTE:The NCA-2 supports'up to 96 annunciator address points Marine Applications:Marine approved systems must be con-
<br /> perACM-24ATI-48A. figured using components I"ternized in this document. (See
<br /> ELECTRICAL SPECIFICATIONS
<br /> Main System Components,In"Product Line Information.)Spa-
<br /> cific,connections and requirements for those components are
<br /> • Primary input p'ower- described in the installation document,PN 54756.When these
<br /> —CPU2-640 board:120 VAC,50/60 Hz,5.0 A. requirements are followed, systems are approved by the foIr
<br /> —CPU2-64.0E board:220/240.VAC,50/60 Hz,2.5 A. [owing agencies:
<br /> • Current draw(staildby/alarm): . US Coast Guard 161.002/50/0,'161.002/55/0(Standard 46
<br /> CPU2-640(E)board:0.250 A.Add 0.035 A for each NAC CFR and 161.002).
<br /> in use. . Lloyd's Register 11/600013(ENV 3 category);
<br /> KDM-R2:0.100 A. . American Bureau of Shipping(ABS)Type-Approval.
<br /> LE.M-320:0.100 A. NOTE.For information on marine applications,see DN-60688.
<br /> • Total output 24 V power:6.0 A in,alarm. STANDARDS
<br /> NOTE. The power supply has a total of 6.0 A.of available power. The NFS2-640 complies with the following UL Standards and
<br /> This is shared by all internal circuits.See Installation Manual fora NFPA 72, Inte m- atiorial Building Code (IBC}, and California
<br /> complete current draw calculation sheet. Building Code(CBib)Fire Alarm Systems requirements:
<br /> . Standard,notification circuits(4):1.5 A each.
<br /> . UL 864,9th Edition(Fire).
<br /> . Resettatile regulated 24V power:1.25 A. . UL 1076(Burglary).
<br /> . TWo'non-resettable regulated.24V power,outputs: . UL 2572 (Mass Notification Systems). (NFS2<640 version
<br /> 1.25 A. 20 or higher.)
<br /> 0.50 A.' LOCAL (Automatic, Manual, Waterflow and Sprinkler
<br /> . Non-resettable 5V power:0.15 A. Supervisory).
<br /> . Battery charger range: 16 AH 200 AH.Use separate cab- AUXILIARY(Automatic, Manual and Waterflow) (requires
<br /> !net for batteries over 26 AH. TM-4).
<br /> - Float rate:27.6 V. REMOTE STATION (Automatic, Manual,.Waterflow and
<br /> CABINET SPECIFICATIONS Sprinkler Supervisory)(requires TM-4).
<br /> • PROPRIETARY(Automatic,Manual and Waterflow).
<br /> Systems:can be installed in CAB-4 Series cabinets (four Not applicable for FM.
<br /> sizes with various door options, see D.N-6857). Requires EMERGENCY VOICE/ALARM.
<br /> BP2-4,Battery Plate.
<br /> OT,pSDN(Other Technologies,Packet-switched Data Net-
<br /> SHIPPING WEIGHT work).
<br /> . CPU2-640/-640: 14.3 lb'(6.49 kg). . IBC 2012,IBC 2009,IBC.2006,IBC'2003,IBC 2000(Seas-
<br /> . CPU2-640/-640E:14.55 lb(6.60 kg). mic).
<br /> TEMPERATURE AND HUMIDITY RANGES CBC 2007(Seismic).
<br /> This system meets NFPA requirements for operation at 0 —
<br /> 49*C/32 — 120°F and at a relative humidity 93% ± 2% RH
<br /> (noncondensing)at 32'C ± 2*13 (90°F±3*F). However, the
<br /> useful life of the system's standby batteries and the electronic
<br /> components may be adversely affected by extreme tempera-
<br /> ture ranges and humidity. Therefore, it is.recommended that
<br /> this system and its peripherals be installed in an environment
<br /> with a normal room temperature of 15—27*C/60—80°F.
<br /> AGENCY LISTINGS AND APPROVALS
<br /> The listings and approvals below apply to,the basic NFS2-640
<br /> control panel. In some cases, certain modules may not be
<br /> listed by certain approval agencies, or listing may be,in pro-
<br /> cess.Consult factory for latest listing status.
<br /> . UL Listed:S635.
<br /> . ULC Listed:S635.
<br /> . FM Approved. intelliQuadTM,NOTI*FIRE*NETTm, ONYXWcirksTm,and SMFTTm are
<br /> trademarks;and Acclimate P PlusTm, FirstCornmandO,FlashScanO,
<br /> . MEA:128-07=E. Inveipent FAAS149, NOTIFIIERI' ONYXP,- VerlFird" Tools, and
<br /> . Fire.Dept.of New York:#6121. V11 are registered trademarks of..Honeywell 'International Inc.
<br /> Microsoft® and'Windows O are.registered trademarks of Microsoft
<br /> . CSFM:7165-0028:0243. Corporation.IBM O is a registered trademark of IBM Corporation.
<br /> - City of Chicago. @2016 by Honeywell International Ind.All rights reserved.Unauthorized use
<br /> of this document Is strictly prohibited.
<br /> This document is not Wended to be used for installation purposes.
<br /> We try to keep our product information up.-to-date and accurate. RRRRRW�
<br /> IS09001 We cannot cover all specific applications.or anticipate all requirements.
<br /> WNHINammm All specifications are subject to change without notice.
<br /> QUALITY SYSTEMS Made In the U.S.A.
<br /> For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118.
<br /> www.notifier.com
<br /> Page 6 of 8—DN-711 11-01/25/2016
<br />
|