Laserfiche WebLink
Manual S Compliance Report Job.- R0420165 <br /> +�+ W Fightsoft, Date: Apr 23,2020 <br /> Entire House By: MKc <br /> GL Steve Construction <br /> 37651 8th Ave,ZepFry Is,FL 33-142 <br /> Project • . • <br /> For. Calvin and Lindsey Doque <br /> 8thAve,Zephyrhills,FL 33542 <br /> Cooling Equipment <br /> Design Conditions <br /> Outdoor design DB: 91.4°F Sensible gain: 24801 Btuh Entering coil DB: 83.1°F <br /> Outdoor design WB: 77.2°F Latent gain: 5096 Btuh Entering coil WB: 65.8°F <br /> Indoor design DB: 75.0'F Total gain: 29897 Btuh <br /> Indoor RH: 50% Estimated airflow: 1140 cFm <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipmenttype: SplitASHP <br /> Manufacturer. 3 Ton Goodman Mfg. Model: GSZ160361 B+ASPT37C14A <br /> Actual airflow: 1140 cfm <br /> Sensible capacity: 24966 Btuh 101%of load <br /> Latent capacity: 9234 Btuh 181%of load <br /> Total capacity: 34200 Btuh 1141/oof load SHR: 730/c, <br /> Heating Equipment <br /> Design Conditions <br /> Outdoor design DB: 42.9°F Heat loss: 20301 Btuh Entering coil DB: 69.7°F <br /> Indoor design DB: 70.00F <br /> Manufacturer's Performance Data at Actual Design Conditions <br /> Equipmenttype: SplitASHP <br /> Manufacturer. 3 Ton Goodman Mfg. Model: GSZ160361 B+ASPT37C14A <br /> Actual airflow: 1140 cfm <br /> Output capacity: 35000 Btuh 172%of load Capacity balance: 29 OF <br /> Supplemental heat required: 0 Btuh Economic balance: -99 OF <br /> Backup equipment type: Elec strip <br /> Manufacturer. Model: <br /> Actual airflow: 1140 cfm <br /> Output capacity: 10.0 kW 168%of load Temp.rise: 44 OF <br /> Meets all requirements ofACCA Manual S. <br /> r wrightsolFt" 2020-Apr-24163500 <br /> ,..•: .„,...w.,, RigttStiL-@Uriversa1201919.0.18 RSU07440 Page 1 <br /> ACC _v60 <br /> ri-Duque-L-E-MailirgC4vd?R0420165.rup Calc=MJ8 FrortDooriaces S <br /> ■ <br />