Laserfiche WebLink
GENERAC" <br /> OFF THE GRID POWER SERVICES <br /> 16450 Spring Valley Road <br /> DADE CITY,FL 33523 <br /> (352)437AS17 <br /> www.ofthegridpowerservices.com <br /> Sizing Report <br /> Rated Nominal Voltage 240 <br /> Generator Fuel Choice Propane <br /> Sizing Method(NEC 220) Part IV <br /> (Part III required for selected circuit implementation,Both valid for whole house) <br /> General Lighting&Receptacles Load(kW) <br /> Square Footage Being Covered(ftA2) 2139 6.417 <br /> Small Appliance Circuits(20 amps) <br /> IGtchen Circuits 2 3 <br /> Laundry Circuits 1 1.5 <br /> Managed Estimated Nameplate <br /> Fixed-In-Place Appliances&Motors Loads (kMf) (amps) 240 V Load(kW) <br /> Microwave 1.3 1.3 <br /> Water Heater 5.0 X 5.0 <br /> Dishwasher 1.5 1.5 <br /> Freezer 0.8 0.8 <br /> Refrigerator 0.8 0.8 <br /> Managed Estimated Nameplate <br /> Air Conditioning&Cooling Loads (k" (amps) 240 V Load(kW) <br /> Managed Estimated Nameplate <br /> Heating&Heat Pumps Loads (kW) (amps) P40 V Load(kW) <br /> Heat Pump(5 Ton) 5.0 X 5.0 <br /> Estimated Actual Utilized <br /> Transient Requirement (LRA) (LRA) (LRA) <br /> Largest Motor's Starting Amps(LRA) 144 0 144 <br /> Load NEC <br /> Summary NEC Load (kW) Required <br /> General Lighting&Receptacles 10.9 <br /> Fixed4n-Place Appliances&Motors 9.4 <br /> Sum of all General Loads 20.3 14.1 <br /> Cooling 0.0 0.0 <br /> Heating(w/demand factors) 5.0 5.0 <br /> Larger of Heating&Cooling 5.0 5.0 <br /> Sizing based on requirements of NEC Article 220,Part IV 19.1 <br /> Elevation 0 It <br /> Minimum size generator for motor starting requirements 20 <br /> BTU load required 325000 <br /> 20 kW Generac Model Generator Recommended <br />