SECTION 3—SYSTEM COMPONENTS R-102 Restaurant Fire Suppression Manual <br /> UL EX3470 ULC EX3470 <br /> PAGE 3-8 REV. 11 2014-SEP-01 <br /> DETECTORS PULLEY ELBOWS <br /> The detector consists of three basic components: the bracket, There are two types of pulley elbows used to change the <br /> linkage,and fusible link.(Fusible links are not included and must direction of the wire rope by 90°.ANSUL recommends for tem- <br /> be ordered separately.) The bracket holds the entire assembly peratures not in excess of 700 °F (371 °C). Part No. 415670 <br /> to the mounting surface. The linkage is used to support the has socket ends with set screws for 1/2 in. conduit, and Part <br /> fusible link.The fusible link is designed to separate at a specific No.423250 has compression ring ends also for 1/2 in.conduit. <br /> temperature and release the wire rope, thereby actuating the Pulley elbows must be ordered in quantities of 50 as Shipping <br /> regulated release mechanism. Assembly Part No. 415671 (socket end type) and Part No. <br /> The scissor style detector allows the wire rope to be strung com- 423251 (compression end type). <br /> pletely through the detection system conduit and brackets first PART NO.415670 PART NO.423250 <br /> and the detector linkage assemblies are then clipped on later. rTT <br /> The detector consists of two types of assemblies: <br /> The Terminal Detector (Part No. 435546) includes a test link 00 <br /> and is placed last in a series of detectors.This detector is some- <br /> times referred to as the end-of-line detector and is thus named <br /> because it is at the point at which the wire rope"terminates,"or <br /> is anchored at the detector bracket. Only one terminal detector FIGURE 3-24 <br /> is required per detection system. 000160/000161 <br /> The Series Detector(Part No.435547)is any detector located PULLEY TEE <br /> in-line between the regulated release assembly and the terminal <br /> detector. The Pulley Tee (Part No.427929)is used to change the direc- <br /> When using Part No. 435546 and 435547 detectors, a total of tion of two wire ropes by 90°. It must be used in areas where <br /> 15 detectors can be in one detection system: 14 series detectors the temperatures are within the range of 32 °F to 130 °F (0 °C <br /> (Part No.435547)and 1 terminal detector(Part No.435546). to 54 °C). Pulley tees can be used in mechanical gas valve <br /> actuation lines and remote manual pull station lines.Pulley tees <br /> Note 1: Series Detector (Part No. 435547) is also available as Part No.435548,25/Pkg. cannot be used within a detection line. <br /> ► Note 2: Scissor-style linkage is also available in a 10-Pack (Part <br /> ►No.439515). <br /> BRACKET E) (D <br /> LINKAGE\ O <br /> FUSIBLE V I FIGURE 3-25 <br /> LINK OD0447 <br /> ►ANSUL STAINLESS STEEL CABLE <br /> FIGURE 3-23 The 1/16 in.stainless steel cable is run from the terminal detec- <br /> 000159 tor, through conduit, all series detectors and pulley elbows, <br /> and into the regulated release mechanism trip lever.When any <br /> fusible link separates, the tension on the cable is relaxed, and <br /> the trip lever actuates the regulated release mechanism. The <br /> cable can also be used for mechanical gas valves and remote <br /> ►manual pull stations. The cable is available in 50 ft (15.2 m) <br /> (Part No. 15821)and 500 ft(152.4 m)(Part No.79653)lengths. <br /> ►The ANSUL stainless steel cable contains a blue tracer cable. <br />