R-102 Restaurant Fire Suppression Manua! SECTION 4—SYSTEM DESIGN <br /> UL EX3470 ULC EX3470 <br /> 2014-SEP-01 REV. 11 PAGE 4-61 <br /> TANK AND CARTRIDGE REQUIREMENTS For higher total flow numbers (23 to 110), multiple cartridges <br /> Once the hazard analysis is completed and the total nozzle flow and regulated actuators are required as shown in the System <br /> numbers are established, the quantity and size of agent tanks Selection Guide in"Appendix"Section <br /> and cartridges needed to supply the nozzles with the prayer <br /> volumes of agent at the proper flow rates can be determined. ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS <br /> For cartridges used in the regulated release mechanism, flow This section contains the guidelines for installing the actuation <br /> capacities, tank quantities and sizes, and regulated release and expellant gas lines between the regulated release mech- <br /> cartridge options are given in the table below. anism regulator, each regulated actuator regulator, and each <br /> Total Quantity and Regulated Release agent tank.These limitations should be considered when select- <br /> Flow Size of Cartridge Options ing the component mounting locations. <br /> Numbers* Tank(s) Nitrogen Carbon Dioxide The actuation gas line is the length of pipe and/or hose that is <br /> 1 — 5 (1) 1.5 Gallon LT 20-R 101-10 run from either the AUTOMAN Regulated Release Assembly or <br /> the Remote Release Assembly that directs high pressure from <br /> 6—11 (1)3.0 Gallon LT-30-R 101-20 the cartridge in the release to actuate one or more additional <br /> 11 —16 (1) 1.5 Gallon Double 101-30 Regulated Actuator Assemblies. The actuation gas line can <br /> (1)3.0 Gallon consist of 1/4 in. Schedule 40 black iron, chrome-plated, stain- <br /> 16—22 (2)3.0 Gallon Double 101-30** less steel, or galvanized steel pipe and fittings, and/or factory <br /> 16—22 (2)3.0 Gallon Double — supplied stainless steel braided actuation hose. <br /> (Manifold) The expellant gas line is the length of pipe that is run from the <br /> 22—33 (3)3.0 Gallon Double — regulator in either the AUTOMAN Regulated Release Assembly <br /> When one or more regulated actuators are used, the following or a Regulated Actuator Assembly that directs regulated pres- <br /> tank and cartridge combinations apply for each regulated actu- sure to the agent storage tanks to pressurize the tank and <br /> ator: discharge the agent. The expellant gas line shall consist of 1/4 <br /> Regulated Actuator Regulated Actuator in. Schedule 40 black iron, chrome-plated, stainless steel, or <br /> Tank(s) Cartridge galvanized steel pipe and fittings. <br /> (1) 1.5 Gallon LT-20-R or 101-10 Actuation Gas Line—6 to 8*Tanks Maximum <br /> (1)3.0 Gallon LT-30-R or 101-20 '8 Tank maximum reflects the utilization of 3 tank regulated actuators. <br /> (1) 1.5 Gallon and LT-A-101-30 or 101-30**or 1. Use only 1/4 in. Schedule 40 black iron, hot-dipped galva- <br /> ( )3.0Gallon double tank <br /> (2)3.0 Gallon LT-A-101-30 or 101-30**or nixed, chrome-plated, or stainless steel pipe and fittings. <br /> double tank 2. The actuation gas line piping is installed from the regulated <br /> (2)3.0 Gallon(Manifold) LT-A-101-30 or Double release mechanism to each regulated actuator connected <br /> (3)3.0 Gallon LT-A-101-30 or Double within the system. The total length of the actuation gas line <br /> For exceptions to maximum flow numbers,see Distribution Piping Requirements for 1.5 from the regulated release assembly to the regulated actua- <br /> gallon and 3.0 gallon Systems in this Section. for assembly(ies)must not exceed 20 ft(6.0 m)when using <br /> ••The 101-30 cartridge can not be used when two 3.0 gallon tanks are manifolded together. an LT 20-R, an LT 30-R nitrogen cartridge,or a 101-10 or a <br /> 101-20 carbon dioxide cartridge. See Figure 4-121. <br /> REGULATED ACTUATOR ASSEMBLY <br /> EXPELLANT GAS LINES <br /> NOT INCLUDED IN ACTUATION `y <br /> GAS LINE LENGTH TOTALS <br /> REGULATED <br /> ACTUATOR <br /> ASSEMBLY <br /> ACTUATION GAS LINE WITH AN LT-2o-R, <br /> LT 30-R,101-10 OR 101-20 CARTRIDGE <br /> MAXIMUM LENGTH OF 20 FT(6.0 m); <br /> MAXIMUM NO.OF FITTINGS 9 <br /> REGULATED <br /> ACTUATOR <br /> ASSEMBLY <br /> AUTOMAN <br /> REGULATED RELEASE <br /> ASSEMBLY <br /> FIGURE 4-121 <br /> coons <br />