Laserfiche WebLink
O <br /> i <br /> { <br /> Single Family Dwelling <br /> Plan Review Comments <br /> 1. FF.E; shall be a minimum of 8" above the road elevation and an engineered site plan. <br /> 2. Lots shall be graded to cortiply with R401.3 of the F.B.C. <br /> 3: Compaction test required if 24" or more of fill dirt is brought in at any one place. <br /> 4. Tie in survey required before pouring concrete. <br /> 5: Driveways require.a R.O.W. use permit. All 4 sides of driveway thru the sidewalk shall have <br /> expansion material. <br /> 6. All setbacks shall be met. <br /> 1. All property markers sliall be uncovered.and marked at time of first inspection. <br /> 8: All A.D.A.-requirements shall be met: <br /> 9. No electric, plumbing,-mechanical, or framing shall be covered without an inspection.and <br /> approval first. <br /> 10. All Garages shall comply with section R302.6 of the F.B.C. (Fite Separation). <br /> 11. Appliances shall not be installed in a location where subject to mechanical damage unless <br /> protected by approved barriers. M303 A of the F.B.0 <br /> 12. Water=heaters shall comply with section P607.3 of the E.B.C: <br /> 13. Foundation supports for A/C units shall be raised at least 3" above finished grade. M1308.1 <br /> 14. Return air in.all bedrooms. F.B.C. M1620.4 <br /> 15. Smoke detectors are to be installed in accordance withF.B.C.R313.1 of the F. <br /> 16:All glazing requirements are to be in accordance with R308.4 of the RB:C. <br /> 17. All means of egress are to be in accordance with R311 of the F.B.C. <br /> 18. "Green gypsum board" shall not be used as a backer in showers or tubs. R702.4.2 F.B.C. <br /> 19: Combination-type AFCI breakers are required at all locations requiring an AFCI type breaker. <br /> 20. Carbon monoxide alarms will be required in new construction that uses fossil-burning heating <br /> or appliances or an attached garage. They shall be-installed in accordance with the F.B.C: <br /> 21. All,plumbing, mechanical, and electrical shall be separate from unit to unit. This includes all <br /> underground plumbing and electric. <br /> 22. All 2016 N.E.C. Codes will be enforced: <br />