Laserfiche WebLink
Envelope Leakage Test Report (Blower Door Test) <br /> Residential Prescriptive, Performance or ERI Method Compliance <br /> 2020 Florida Building Code, Energy Conservation, 7th Edition <br /> Jurisdiction: Permit#: <br /> -Job Information <br /> Builder: DR Horton Community: Lot: 16/14 <br /> Address: <br /> City: Zephyrhills State: FL Zip: <br /> Alr`Leakage Test, ReSUItS Passing results must meet either the Performance; Prescriptive,or ERI Method <br /> O PRESCRIPTIVE METHOD-The building or dwelling unit shall be tested and verified as,having an-air leakage rate of not exceeding 7 air; <br /> changes per hour at a pressure of.0.2 inch w.g.;(50 Pascals)in Climate Zones 1.,and 2. - <br /> Q.. PERFORMANCE or..ERI METHOD-The build1.ing or dwelling unit shall be�tested and,verified as having an.air leakage rate of not exceeding <br /> the selected ACH(50)value,as shown:on Form R405-202D(PerfoFinance)or h406-2020(ERI),section labeled as infiltration,sub-sect!on ACH50: <br /> ACH(50)specified on Form R405-2020-Energy Palo(Performance)or R406-2020(ERI): 7.000 <br /> x 60 - 26375 — Method for calculating building volume: <br /> CFM(50) Building Volume ACH(50) O Retrieved from architectural plans <br /> 1-1 PASS •Code software calculated <br /> When ACH(50) is less than 3, Mechanical Ventilation installation O Field measured and calculated <br /> must be verified by building department. <br /> R402.4.1.2 Testing.Testing shall be conducted in accordance with ANSI/RESNET/ICC 380 and reported at a pressure of 0.2 inch w.g.(50 Pascals) <br /> Testing shall be conducted by either individuals as defined in Section 553.993(5)or(7),Florida Statues.or individuals licensed as set forth in Section <br /> 489.105(3)(f), (g),or(i)or an approved third party.A written report of the results of the test shall be signed by the party conducting the test and <br /> provided to thecode official.Testing shall be performed at any time after creation of all penetrations of the building thermal envelope. <br /> During testing: <br /> 1.Exterior windows and doors,fireplace and stove doors shall be closed,but not sealed,beyond the intended weatherstripping or other infiltration <br /> control measures. <br /> 2.Dampers including exhaust,intake,makeup air,back draft and flue dampers shall be closed,but not sealed beyond intended infiltration control <br /> measures. <br /> 3.Interior doors,if installed at the time of the test,shall be open. <br /> 4.Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed. <br /> 5.Heating and cooling systems,if installed at the time of the test,shall be turned off. <br /> 6.Supply and return registers,if installed at the time of the test,shall be fully open. <br /> Testing Company <br /> Company Name: Phone: <br /> I hereby verify that the above Air Leakage results are in accordance with the 2020 7th Edition Florida Building Code <br /> Energy Conservation requirements according to the compliance method selected above. <br /> Signature of Tester: Date of Test: <br /> Printed Name of Tester: <br /> License/Certification#: Issuing Authority: <br /> 2/8/2021 1:28:59 PM EnergyGauge@ USA 7.0.00-FlaRes202O FBC 7th Edition(2020)Compliant Software Page 1 of 1 <br />