My WebLink
|
Help
|
About
|
Sign Out
Browse
Search
20-1119
Zephyrhills
>
Building Department
>
Permits
>
2020
>
20-1119
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
5/27/2022 8:02:13 AM
Creation date
5/27/2022 8:02:11 AM
Metadata
Fields
Template:
Building Department
Building Department - Doc Type
Permit
Permit #
20-1119
Building Department - Name
ROSSELLO ANGELO & RUTH E LIVING TRUST
Address
5424 10TH ST
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
28
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
MANDATORY REQUIREMENTS - (Continued) <br /> ❑R402.4.4 Rooms containing fuel-burning appliances. In Climate Zones 3 through 8,where open combustion air ducts provide combustion air to <br /> open combustion fuel burning appliances,the appliances and combustion air opening shall be located outside the building thermal envelope or <br /> enclosed in a room,isolated from inside the thermal envelope.Such rooms shall be sealed and insulated in accordance with the envelope requirements <br /> of Table R402.1.2,where the walls,floors and ceilings shall meet not less than the basement wall R-value requirement.The door into the room shall be <br /> fully gasketed and any water lines and ducts in the room insulated in accordance with Section R403.The combustion air duct shall be insulated where it <br /> passes through conditioned space to a minimum of R-8. <br /> Exceptions: <br /> 1. Direct vent appliances with both intake and exhaust pipes installed continuous to the outside. <br /> 2. Fireplaces and stoves complying with Section R402.4.2 and Section R1006 of the Florida Building Code,Residential. <br /> ❑R402.4.5 Recessed lighting. Recessed luminaires installed in the building thermal envelope shall be sealed to limit air leakage <br /> between conditioned and unconditioned spaces.All recessed luminaires shall be IC-rated and labeled as having an air leakage rate not <br /> more than 2.0 cfm(0.944 Us)when tested in accordance with ASTM E283 at a 1.57 psf(75 Pa)pressure differential.All recessed <br /> luminaires shall be sealed with a gasket or caulk between the housing and the interior wall or ceiling covering. <br /> SECTION R403 SYSTEMS <br /> R403.1 Controls. <br /> ❑ R403.1.1 Thermostat provision(Mandatory). At least one thermostat shall be provided for each separate heating and cooling system. <br /> ❑ R403.1.3 Heat pump supplementary heat(Mandatory). Heat pumps having supplementary electric-resistance heat shall have controls <br /> that,except during defrost,prevent supplemental heat operation when the heat pump compressor can meet the heating load. <br /> ❑ R403.3.2 Sealing(Mandatory) All ducts,air handlers,filter boxes and building cavities that form the primary air containment passageways <br /> for air distribution systems shall be considered ducts or plenum chambers,shall be constructed and sealed in accordance with Section <br /> C403.2.9.2 of the Commercial Provisions of this code and shall be shown to meet duct tightness criteria below. <br /> Duct tightness shall be verified by testing in accordance with ANSI/RESNET/ICC 380 by either individuals as defined in Section 553.993(5)or <br /> (7),Florida Statutes,or individuals licensed as set forth in Section 489.105(3)(f),(g)or(i),Florida Statutes,to be"substantially leak free"in <br /> accordance with Section R403.3.3. <br /> ❑ R403.3.2.1 Sealed air handler. Air handlers shall have a manufacturers designation for an air leakage of no more than 2 percent <br /> of the design airflow rate when tested in accordance with ASHRAE 193. <br /> ❑ R403.3.3 Duct testing(Mandatory).Ducts shall be pressure tested to determine air leakage by one of the following methods: <br /> 1. Rough-in test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the system, <br /> including the manufacturers air handler enclosure if installed at the time of the test.All registers shall be taped or otherwise <br /> sealed during the test. <br /> 2. Postconstruction test:Total leakage shall be measured with a pressure differential of 0.1 inch w.g.(25 Pa)across the entire <br /> system,including the manufacturers air handler enclosure.Registers shall be taped or otherwise sealed during the test. <br /> Exceptions: <br /> 1. A duct air leakage test shall not be required where the ducts and air handlers are located entirely within the building <br /> thermal envelope. <br /> 2. Duct testing is not mandatory for buildings complying by Section 405 of this code.Duct leakage testing is required for Section <br /> R405 compliance where credit is taken for leakage,and a duct air leakage Qn to the outside of less than 0.080(where Qn= <br /> duct leakage to the outside in cfm per 100 square feet of conditioned floor area tested at 25 Pascals)is indicated in the <br /> compliance report for the proposed design. <br /> A written report of the results of the test shall be signed by the party conducting the test and provided to the code official. <br /> ❑R403.3.5 Building cavities(Mandatory). Building framing cavities shall not be used as ducts or plenums. <br /> ❑R403.4 Mechanical system piping Insulation(Mandatory). Mechanical system piping capable of carrying fluids above 105°F(41°C) <br /> or below 55°F(13°C)shall be insulated to a minimum of R-3. <br /> ❑ R403.4.1 Protection of piping Insulation. Piping insulation exposed to weather shall be protected from damage,including that <br /> caused by sunlight,moisture,equipment maintenance and wind,and shall provide shielding from solar radiation that can cause <br /> degradation of the material.Adhesive tape shall not be permitted. <br /> ❑ R403.5.1 Heated water circulation and temperature maintenance systems(Mandatory). If heated water circulation systems are <br /> installed,they shall be in accordance with Section R403.5.1.1.Heat trace temperature maintenance systems shall be in accordance with <br /> Section R403.5.1.2.Automatic controls,temperature sensors and pumps shall be accessible.Manual controls shall be readily accessible. <br /> R403.5.1.1 Circulation systems. Heated water circulation systems shall be provided with a circulation pump.The system return pipe shall <br /> ❑ be a dedicated return pipe or a cold water supply pipe.Gravity and thermosiphon circulation systems shall be prohibited.Controls for <br /> circulating hot water system pumps shall start the pump based on the identification of a demand for hot water within the occupancy.The <br /> controls shall automatically turn off the pump when the water in the circulation loop is at the desired temperature and when there is no <br /> demand for hot water. <br /> ❑ R403.5.1.2 Heat trace systems.Electric heat trace systems shall comply with IEEE 515.1 or UL 515.Controls for such systems shall <br /> automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping in accordance with the <br /> times when heated water is used in the occupancy. <br /> 2/5/2021 11:08 AM EnergyGauge®USA 7.0.00-FlaRes2020 FBC 7th Edition(2020) Compliant Software Page 2 of 5 <br />
The URL can be used to link to this page
Your browser does not support the video tag.